TECHNICAL FEATURES
MODEL
A03-OP6000
Power Rating
6000 VA - 4200 W
INPUT
Voltage (Vac) 160-280
Frequency (Hz) 50 ± 5% (Auto Sensing)
Phase SingleLine+Neutral+Ground
Input Power Factor > 0.99 (Full Load)
OUTPUT
Voltage (Vac) 220/230/240
Voltage Regulation ± 2%
Voltage Adjustement ± 0%; ± 1%; ± 2%; ± 3%
Frequency Stability ±0.2% (Free Running)
Frequency Regulation ± 1%; ± 3%
Wave Form Sine Wave, THD<4%
(no load to full load)
Rated Power Factor 0.7
Transfer Time 0 ms
Crest Factor 3:1
Efficiency (AC to AC) >90% (Normal)
Efficiency
(AC to AC, ECO)
>98% (ECO)
Run Time (Full Load) > 8 min
DC Start Yes
BATTERY
Type Maintenance Free Sealed
Lead Acid
Quantity (pcs) 20
Voltage (Vdc) 240
Recharge Time 4 Hours to 90%
Supplem. Charger Optional 1000W Isolated
chargers
PROTECTION
Short Circuit Hold Whole System
OverHeat Switch to Bypass
High Voltage Trip Switch to Backup Mode
Battery Low Alarm and Switch Off
Noise Suppression Complies with EN50091-2
Spike Suppression Complies with EN610000-4-5
OverLoad AC Mode:
1) <105% continuously Alarm
2) 105%-150% delay 40
seconds before switching to bypass
4) >150% immediately
switching to bypass
Backup Mode: Same Delay
Time as AC Mode, then
completely shutdown
MODEL
A03-OP6000
ALARMS
Audible and Visual Line Failure, Battery Low, Tranfer to Bypass,
System Fault Conditions
DISPLAY
Self Diagnostics Push Button (On Demand)
LED+LCD Utility, Battery, Inverter, Bypass, Self-Test,
OverLoad, Load/Battery Level and Fault
PHYSICAL
Dim (WxDxH) 290 x 645 x 748 mm
Outlets Terminal Block
Net Weights (Kgs) 80
ENVIRONMENTAL
Operating
Temperature
0-40
o
C
Temperature Warning The battery design life is based on a
temperature of 25
o
°C. Ambient temperature
above this range will reduce battery life
Altitude / Humidity 0-2000m up to 40°C, 3000m up to 35°C /
90% RH Humidity max (non-condensing)
Noise < 45 dB (at 1 metere)
COMPUTER
INTERFACE
Interface Type Standard RS232 Interface / SNMP
Protocol MEGATEC Protocol
AS 400 Interface Optional As400/ Basic Photo Contact
Interface Board provides Utility Failure,
Battery Low, Bypass Active, UPS
Shutdown functions
SNMP Adaptability Slot for Standard SNMP Card
Compatibility of
Bundled Software
UPSilon2000 for: Novell NetWare,
Windows95/98, Windows NT, Windows ME,
Windows 2000 and XP, Linux and FREE BSD
Optional Software UPSilion for UNIX, SNMP Adapter, USBMate
SAFETY
CONFORMANCE
Quality Assurance ISO9001 Certified Company
Marks CE