Cisco Systems IGX 8 Switch User Manual


 
-2 IGX Installation Manual, Release 8.2.3
General IGX 16/32 Specifications
DC Input Connections 3-wire pluggable terminal block with screw terminal connectors.
Operating Environment: 0° to 40° C (32° to 104° F) normal operation (50° C up to 72 hours).
Maximum 85% relative humidity.
Shock: Withstands 10 G, 10 ms. at 1/2 sine wave.
Vibration: Withstands 1/4 G, 20–500 Hz.
Heat Transfer to Room: IGX 8: 2720 BTUs max.
System Capacity: 1 or 2 shelves, each with 16 card slots.
Requires 1 or 2 dedicated front slot(s) for NPMs.
Requires 1 dedicated back slot for SCM.
Up to 16 T1/E1 circuit ports.
Up to 16 T1/E1 packet trunks.
Up to 100 synchronous data ports.
Up to 25 Voice, Data, and/or Frame Relay Module groups.
Enclosure Size: IGX 16 Standalone/Rackmount:
HT: 32.25 ins. (82 cm.), standalone; 31.75 ins. (80.7 cm.), rack
WD: 19.9 inches (50.5 cm), standalone; 19 inches (48.3 cm.), rack
DP: 26.75 inches (68 cm), standalone; 26 inches (66 cm.), rack
IGX 32 Standalone/Rackmount:
HT: 55.5 inches (141 cm.), standalone, 55 inches (139.7 cm) rack
WD: 19.9 inches (50.5 cm), standalone; 19 inches (48.3 cm.), rack
DP: 26.75 inches (68 cm), standalone; 26 inches (66 cm.), rack
Shipping Weight: 600 pounds (270 kilos) for a fully loaded IGX 32.
400 pounds (180 kilos) for a fully loaded IGX 16.
Clearance Requirement: At least 30 inches front and rear clearance; nominal
12 inch side clearance.
Power Input Voltage: AC system: 180 to 264 VAC, 47 to 63 Hz.
DC system: –42 to –56 VDC.
Each AC supply can provide up to 875 watts to a card shelf. Cabinet
has space for 6 AC power supplies.
Current Requirements: Configuration dependent: use Network Design Tool for exact
requirements. For planning purposes, use the following:
AC System IGX 16/32: 16 Amps maximum at nominal voltage of 180 VAC.
DC System IGX 16: 24 Amps max. per circuit at –42 VDC (worst case)
IGX 32: 44 Amps at nominal –48 VDC; 50 Amps at –42 VDC
maximum per circuit at –42 VDC.