EDS Series Factory Sealed
Manual Motor Starting Switches
and Enclosures
Ordering Information
With Allen-Bradley Bulletin 600 Switches
Maximum HP Ratings
Poles
115–230
Volts AC
115–230
Votts DC Cat. #
11 hp A B BUL 600 TOX4
21 hp
3
/4 hp A B BUL 600 TOX5
Poles
Hub
Size in. Dead end Cat. # Through feed Cat. #
Single Gang
1
3
/4 EDS2199 EDSC2199
1 EDS3199 EDSC3199
2
3
/4 EDS21100 EDSC21100
1 EDS31100 EDSC31100
Two Gang
1
3
/4 EDS2299 EDSC2299
1 EDS3299 EDSC3299
2
3
/4 EDS22100 EDSC22100
1 EDS32100 EDSC32100
Heater Table (Allen-Bradley)
Max. Motor
Full-Load
Amps
Crouse-Hinds
Symbol Number
Max. Motor
Full-Load
Amps
Crouse-Hinds
Symbol Number
0.17 P1 2.92 P22
0.21 P2 3.09 P23
0.25 P3 3.32 P24
0.32 P4 3.77 P25
0.39 P5 4.16 P26
0.46 P6 4.51 P27
0.57 P7 4.93 P28
0.71 P8 5.43 P29
0.79 P9 6.03 P30
0.87 P10 6.83 P31
0.98 P11 7.72 P32
1.08 P12 8.24 P33
1.19 P13 8.9 P34
1.30 P14 9.6 P35
1.43 P15 10.8 P36
1.58 P16 12.0 P37
1.75 P17 13.5 P38
1.88 P18 15.2 P39
2.13 P19
2.40 P20
2.58 P21
With General Electric Switches
Maximum HP Ratings
Poles
115–230
Volts AC
115
Votts DC
230
Votts DC Cat. #
1 1 hp 1 hp
1
/4 hp GE CR101 Y
2 1 hp 1 hp 1 hp GE CR101 H
Poles
Hub Size
in. Dead end Cat. # Through feed Cat. #
Single Gang
1
3
/4 EDS21093 EDSC21093
1 EDS31093 EDSC31093
2
3
/4 EDS21094 EDSC21094
1 EDS31094 EDSC31094
Two Gang
1
3
/4 EDS22093 EDSC22093
1 EDS32093 EDSC32093
2
3
/4 EDS22094 EDSC22094
1 EDS32094 EDSC32094
Heater Table (General Electric)
Max. Motor
Full-Load
Amps
Crouse-Hinds
Symbol Number
Max. Motor
Full-Load
Amps
Crouse-Hinds
Symbol Number
.48 G2 3.01 G22
.53 G3 3.27 G23
.58 G4 3.56 G24
.65 G5 3.88 G25
.71 G6 4.22 G26
.78 G7 4.60 G27
.86 G8 5.00 G28
.95 G9 5.43 G29
1.04 G10 5.90 G30
1.14 G11 6.41 G31
1.25 G12 6.98 G32
1.37 G13 7.60 G33
1.49 G14 8.25 G34
1.63 G15 8.95 G35
1.78 G16 9.75 G36
1.95 G17 10.6 G37
2.13 G18 11.4 G38
2.32 G19 12.5 G39
2.53 G20 13.6 G40
2.76 G21 14.8 G41
16.0 G42
Cl. I, Div. 1 & 2, Groups B*, C, D
Cl. II, Div. 1, Groups E, F, G
Cl. II, Div. 2, Groups F, G
Cl. III
NEMA 3, 7B*CD, 9EFG
Explosionproof
Dust-Ignitionproof
Raintight
Wet Locations
*Add GB suffix. Seals must be installed within 1
1
/2" of each conduit opening for Group B usage.
Includes one interchangeable heater. Select heater from the table
below individual listings and use symbol number as second section
of the Cat. No. Example: EDS2199-P5. Insert symbol 0 (zero) to omit
heater.
These heaters are for motors rated 40°C continuously. For motors
rated 50°C or 55°C, multiply full load motor current by 0.9 and use
this value to select heaters. Symbol 0 (zero) must be used to indicate
heater omitted.