Dell J730N Power Supply User Manual


 
43
Operation
|
Table 6. Settings (continued)
Description Default SettingAvailable Settings
Overload Alarm Level [10%] [20%] [30%]...[100%]
If 100%, the UPS issues an Output Overload alarm
at load > 100%.
NOTE: Output Overload Level 1 by default is set to
100% and is configurable from 10% to 100% in 10%
increments through the LCD setting menu. This
allows customers to be alerted before the UPS has
reached its rated capacity limits.
100%
Power Strategy [Normal] [High Efficiency] [Converter]
See “Setting Power Strategy” on page 47.
High Efficiency
Automatic Start Delay [Off] [0s] [1s] [2s]...[32767s]
See “Configuring Load Segments” on page 49.
0s
Automatic on Battery Shutdown [Off] [0s] [1s] [2s]...[32767s]
See “Configuring Load Segments” on page 49.
Off
Start on Battery [Enabled] [Disabled]
NOTE: Battery start is disabled from the factory and
remains disabled until the UPS has been powered
from utility and enters Standby mode. After the
UPS has been started once from utility, the Start on
Battery feature is automatically enabled. After this is
set by the user, it remains set.
Enabled
Battery Saving Mode [Disabled] [10%] [20%] [30%]...[100%]
The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.
Disabled
On Battery Notice Delay [0] [1s] [2s]...[99s]
The UPS issues a “UPS on battery” notice in the
specified number of seconds after the UPS starts to
discharge the batteries.
0s
Site Wiring Fault Alarm [Enabled] [Disabled] Enabled for low
voltage models;
Disabled for all other
models