Environmental
Operating Continuous operation: 10 °C to 35 °C at 10% to 80%
relative humidity (RH), with 26 °C max dew point. De-rate
maximum allowable dry bulb temperature at 1 °C/300 m
above 900 m (1 °F per 550 ft).
NOTE: For information on supported expanded
operating temperature range and configurations, see
support.dell.com/manuals.
Storage –40 °C to 65 °C (–40 °F to 149 °F) with a maximum
temperature gradation of 20 °C per hour
Relative humidity
Operating 20% to 80% (noncondensing) at a maximum wet bulb
temperature of 29 °C (84.2 °F)
Storage 5% to 95% at a maximum wet bulb temperature of 38 °C
(100.4 °F)
Maximum vibration
Operating 0.26 Grms at 5–350 Hz (all operation orientations)
Storage 1.87 Grms at 10–500 Hz for 15 min (all six sides tested)
Maximum shock
Operating One shock pulse in the positive z axis (one pulse on each
side of the system) of 31 G for 2.6 ms in the operational
orientation
Storage Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 71 G for up to 2 ms
Six consecutively executed shock pulses in the positive
and negative x, y, and z axes (one pulse on each side of
the system) of 32 G faired square wave pulse with
velocity change at 270 inches/second (685 centimeters/
second)
Altitude
Operating –15.2 m to 3048 m (–50 ft to 10,000 ft)
NOTE: For altitudes above 2950 ft, the maximum
operating temperature is derated 1ºF/550 ft.
Storage –15.2 m to 10,668 m (–50 ft to 35,000 ft)
Airborne Contaminant Level
Class G1 as defined by ISA-S71.04-1985
8