Delta Electronics 3KVA Power Supply User Manual


 
DELTA DOC CENTER
15
3. Charging the battery
{
The battery charger of the UPS automatically charges the battery whenever the power
cord of UPS is connected to a acceptable utility power.
{
When UPS is running for the first time, charge the UPS for at least 6 hours to ensure
batteries inside are fully charged before operation.
{
You may immediately use the UPS without having to wait for the batteries to be fully
charged. However, it is advisable not to do this as UPS will have a shorter back-up time
than expected if such action is taken.
Connecting the battery bank
1. Utilize the battery connection cable packed with the battery bank.
2. Connect on one end of the cable to the external battery connector of UPS, and the
other end to that of the battery bank.
3. Warning: For safety reason, the manufacturer suggests that ONE UPS
CONNECTS AS MANY AS FIFTEEN EXTERNAL BATTERY BANKS.
Fig 3-3 UPS Connected to External Battery Bank
4. The battery banks should be installed by service personnel.
A. According to UL 1778 safety requirement: in order to remove the battery
power cord emergently, please plug in the power cord directly.
B. According to EN50091-1-1 safety requirement: beside plugging in the battery
power cord, the battery power cord need to be fixed with the screws.
4. Connecting the load
{
Calculate power consumption of your loads to ensure that the overload condition will
not happen.
{
Plug the power cord of the equipment into the output receptacles on the rear panel of the
UPS.
SHEET 16 TO 17