Delta Electronics DVP08ST11N Switch User Manual


 
2
Electrical Specifications
Model
Items
DVP08ST11N
Power voltage 24VDC (-15% ~ 20%) (Power is supplied by the internal bus of MPU)
Power consumption
0.5W
Noise immunity
ESD(IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT(IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV,
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Operation/storage
Operation : 0°C ~ 55°C (Temperature), 50 ~ 95% (Humidity), Pollution degree 2
Storage: -40°C ~70°C (Temperature), 5 ~ 95% (Humidity)
Vibration/ Shock
immunity
International standard: IEC1131-2, IEC 68-2-6 (TEST Fc)/IEC1131-2 & IEC 68-2-27 (TEST Ea)
Weight (g) 60g
How to Install
1. Use a screwdriver
to open the side
cover and reveal
the connecting
port.
2. Use the
screwdriver to lift
and unfasten the
fixing clip.
3. Accurately
connect the
extension module
to the MPU by
using the pinholes
at each corner.
4. Secure the
extension module
to the MPU by
pushing down the
fixing clips.
5. Order of the I/O point No.: The input points of the first extension module are lined up from X20 and output points are
lined up from Y20. The rule applies to all MPU connections with extension modules of any number of points.
Model Input points Output points No. of input points No. of output points
DVP12SA11R 8 4 X0 ~ X7 Y0 ~ Y3
DVP08ST11N 8 0 X20 ~ X27 -
DVP16SP11R 8 8 X30 ~ X37 Y20 ~ Y37
Troubleshooting
Input LED Indicator
The On/Off of input signals can be indicated by the input LED indicator. When the input is On, the LED will be on. If error
occurs, please check if the loops of the LED and input signal are normal by using HPP/WPL. Please also be aware that:
1. Do NOT place DVP08ST11N under direct sunlight and please avoid placing it next to overheating objects in
case the high temperature will affect the functions of DVP08ST11N.
2. Please clean the airborne or conductive dust on the panel on a regular basis.
The content of this instruction sheet may be revised without prior notice. Please consult our distributors or
download the most updated version at http://www.delta.com.tw/industrialautomation