Eaton Electrical 9135 Power Supply User Manual


 
5
www.powerware.com 1.800.356.5794
Technical specifications
General
User interface Graphical LCD with blue backlight and text in English,
French, German, Portuguese, Italian and Spanish
LEDs Four status-indicating LEDs
Topology Double-conversion
Diagnostics Full system self-test
UPS bypass Automatic bypass
Dimensions See model selection guide
Rail kit Included with all units
Electrical input
Nominal voltage 208V, 230V
200V, 208V, 220V, 230V, 240V and 250V
user-selectable
Voltage range 156–280 Vac (output PF 0.7)
Power draw of 5000 VA: 24.0A @208V
UPS (full load) 6000 VA: 28.8A @208V
Recommended 35A
input breaker
rating
Frequency 50/60 Hz autoselect
Frequency range 40–70 Hz
Electrical output
Power factor 0.7
On utility voltage ±2% of nominal
regulation
On battery ±2% of nominal
voltage regulation
Efficiency >97% in high-efficiency mode; 91% in normal mode
Frequency ±3% Hz online
regulation
Load crest 3 to 1
factor
Battery
Internal battery 5.5 Ah, sealed, lead-acid; maintenance free
type
External battery Up to four per 9135, rail kits included for
modules rack mounting
EBM battery type 5.5 Ah, sealed, lead-acid; maintenance free
Battery runtime Four (4) minutes with internal batteries @100%
load (0.7 PF)
For additional details, see battery runtime chart
Battery recharge Six (6) hours to recover 90 percent of nominal backup
time time after 100 percent RCD load discharge
Battery Hot-swappable internal and external batteries
replacement
Start-on-battery Allows start of UPS without utility input
Communications
Serial port RS-232 as standard, RS-232 cable provided
USB port As standard (HID)
Relay output DB-9 Dry Contact—common alarm as standard
Communications Optional communication slots (Mini X-Slot)
slot
Software LanSafe UPS monitoring and management software
Environmental
Safety markings 208V: UL, NOM, NYCE
230V: CE, C-Tick, UL, GS
EMC markings 208/230V: FCC-A, VCCI-A, BSMI-A, C-Tick,
CE Compliance
Audible noise Max 46 dB
Ambient 0˚C (32˚F) to +40˚C (104˚F)
operating
Storage -20˚C (-4˚F) to +40˚C (104˚F) with batteries and
temperature -25˚C (-13˚F) to +55˚C
(131˚F) without batteries
Relative humidity 5–90% non-condensing
Heat dissipation (BTUs/hour)
Operating mode Efficiency 5 kVA 6 kVA
Normal 91% 1150 1350
Battery 86% 1650 1960
High efficiency 97% 370 450
Back panel configurations
Choose from a variety of output receptacle combinations.
Back panel configurations vary by model type.
Hardwired models—230V
Hardwired models—208V
Power-corded models—208V