Eaton Electrical 9825 Power Supply User Manual


 
UPS Rating (0.9 power factor)
kVA 225 275 550
kW 202 250 500
General Characteristics
Efficiency Up to 95%
Parallel Capability Up to 3 modules, 550 kVA maximum
Audible Noise < 65dBA @ 1 meter
Altitude (max) 2000m at 40ºC (104ºF)
N+1 Redundancy Capable Yes
Field Upgradeable Yes, 275 kVA increments
System Bypass Module Included
Input Characteristics
Voltage 480V standard; 208V and 600V with isolation
transformer option
Voltage Range +10% / -15%
Frequency Range 55-65 Hz
Power Factor 0.99 (minimum)
Input Current Distortion <3% (no input filter required)
Soft Start Capability Yes
Internal Backfeed Yes
Protection
Output Characteristics
Voltage 480V standard; 208V and 600V with isolation
transformer option
Regulation ±1%
Inverter PWM with IGBT switching
Voltage THD <2% (100% linear load); <5% (non-linear load)
Load Power Factor Range Up to a .9 power factor leading without de-rating
Battery
Battery Types VRLA, AGM, Gel, Wet
Battery Voltage 480V
Temperature Compensation Optional
Charging Method Advanced Battery Management technology
Dimensions & Weights
225 kVA, 275 kVA 52.4”w x 34.3”d x 73.7”h 1786 lb.
225 kVA redundant, 73.7”w x 34.3”d x 73.7”h 2875 lb.
275 kVA redundant
550 kVA 73.7”w x 34.3”d x 73.7”h 2977 lb.
550 kVA redundant 95.0”w x 34.3”d x 73.7”h 4153 lb.
Field upgrade module, 21.3”w x 34.3”d x 73.7”h 1176 lb
225 or 275 kVA
User Benefits
Control Panel (LCD) 8 lines x 40 characters
Battery Startup Standard
Frequency Conversion Standard
Remote Display Panel Optional
Multi-language Standard
Building Alarm Inputs 6 (galvanic isolated)
Serviceability
Back/Side Against Wall Standard
Installation
Options
External Maintenance Bypass
Powerware PDU, RPP, and STS
Isolation Transformer
Output Transformer
Maintenance Bypass Module
Certifications
Safety UL1778, cUL
EMC FCC Class, A
Surge ANSI C62, 41 Cat, A&B
eNotify Remote Monitoring
24x7 remote monitoring of 43 UPS and battery alarms, daily heartbeat check
and monthly report ConnectUPS Web/SNMP/xHub card
Communications
Software Compatibility - PowerVision
®
, LanSafe
®
,
FORESEER
®
, Power Xpert
Communication Cards - Standard system includes one ConnectUPS Web/SNMP card
with an Environmental Monitoring Probe. Four communication bays standard.
The following connectivity options can be installed at any time:
- ConnectUPS Web/SNMP/xHub
- Modus Card
- Relay Interface Card (Use for AS400s)
- Industrial Relay Card (5A@120V)
- Hot Sync CAN Bridge Card provides CAN communications, isolated RS-485 port
- Environmental Monitoring Probe (EMP)
3
Remote Inputs/Outputs - Six building alarms inputs and one summary alarm contact
(5A@120V) standard
Remote Panel - Eight backlit status indicator lamps plus an audible horn
3
Technical Specifications
2
© 2007 Eaton Corporation
All Rights Reserved
Printed in USA
9395FXA
March 2007
EUROPE/MIDDLE EAST/AFRICA
Denmark: 45.3686.7910
Finland: 358.94.52.661
France: 33.1.6012.7400
Germany: 49.7841.666.0
Italy: 39.02.66.04.05.40
Norway: 47.23.03.65.50
Sweden: 46.8.598.940.00
United Kingdom: 44.1753.608.700
ASIA PACIFIC
Australia/NZ: 61.2.9693.9366
China: 86.21.6361.5599
HK/Korea/Taiwan: 852.2745.6682
India: 91.11.2649.9414 to 18
Singapore/SEA: 65.6825.1668
Powerware, PowerVision, FORESEER, Power
Xpert, LanSafe, and ABM are trademarks of
Eaton Electrical Inc.
2. Due to continuing improvements, specifications are
subject to change without notice.
3. Requires the ConnectUPS Web/SNMP/xHub card.
Powerware® 9395-825 - Available Fall 2008
Uninterruptible Power System (UPS)
225 to 825 KVA
For additional information, please call 1-800-392-3299 or email info@naat.com www.naat.com