Emerson 12-20kVA Power Supply User Manual


 
Emerson Network Power.
The global leader in enabling Business-Critical Continuity
.
EmersonNetworkPower.com
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Racks & Integrated Cabinets
Services
Precision Cooling
Surge Protection
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 Gloucester Rd, Wanchai
Hong Kong
852 25722201 Phone
852 28029250 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2007 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert and the Liebert logo are registered trademarks
of the Liebert Corporation.
SL-23900 (R03/07) Printed in USA
Ensuring The High Availability Of
Mission-Critical Data And Applications
Scalable 12 - 20 kVA
Scalable 4 - 16 kVA
Specifications
General & Environmental Units
Unit Rating kVA 4 8 12 16 20
kW 2.8 5.6 8.4 11.2 14
Conducted and Radiated EMC Levels FCC Part 15, Class A
Compliant Safety Standards UL 1778; c-UL
Compliant Immunity Standards IEEE C62.41, Category B
Mechanical Units 8 Bay 12 Bay
Dimensions: Width 20 (508) 20 (508)
Dimensions: Depth In (mm) 28 (711) 28 (711)
Dimensions: Height 41 (1041) 54 (1372)
Environmental Units 4 8 12 16 20
Operating Temperature (max) F (C) 32°-104° (0°-40°)
Relative Humidity 0-95% non-condensing
Maximum Operating Altitude Ft. (M) 10,000 (3,000)
Nominal Heat Dissipation BTU/Hr 1062 2124 3186 4248 5307
Input Data Units
Nominal Input Voltage VAC 170 to 276
VAC 110-276 (variable, based on output load)
Power Factor Cos 0/ >.98
Input Frequency (nominal) Hz 60
Input Frequency Range Hz 40-70
Battery Module Units
Battery Capacity A/hr 9
Autonomy Time (full load) Mins 7
(With an equal number of Battery & Power Modules, in a non-redundant configuration)
Maximum Charge Current (full load) A 3
Nominal Voltage VDC 120
Recharge Time Hrs 3-5 (to 90% capacity)
Output Data Units
Output Voltage VAC 208/120 or 240/120
Voltage Regulation % ±3
Voltage Transient Response (100% step load) % ±7
Voltage Stability (100% step load) % ±7
Recovery Time msec 96
Voltage distortion: % <3 THD, linear load
<7 THD, non-linear load
Output Frequency Hz 60
Efficiency at 100% load % 89
Output Overload Capability % 110-125% for 10 min
126-150% for 10 sec
>151-200% for 2 cycles