Emerson 3000 Power Supply User Manual


 
Specifications
22
8.0 SPECIFICATIONS
Table 6 Liebert PSI XR specifications
Model Number
PS1000RT3-120XR
PS1000RT3120XRW
PS1500RT3-120XR
PS1500RT3120XRW
PS2200RT3-120XR
PS2200RT3120XRW
PS3000RT3-120XR
PS3000RT3120XRW
Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W
*
3000VA/2700W
Dimensions, W x D x H, in (mm)
Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88) 17.3 x 27.6 x 3.5 (440 x 700.5 x 88)
Shipping 22 x 24.1 x 9 (560 x 612 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228)
Weight, lb (kg)
Unit 56 (25) 62 (28) 92 (42) 105 (48)
Shipping 64 (29) 70 (32) 101 (46) 115 (52)
Input AC Parameters
Surge Protection 570J
Voltage Range
Without Battery Operation
83-159 VAC (configurable)
Frequency Range 45~65Hz, (±0.5Hz)
Input Power Cord,
10ft (3m) attached
NEMA 5-15P plug NEMA 5-20P plug NEMA L5-30P plug
Output Receptacles (6) NEMA 5-15R
(4) NEMA 5-15R
(2) NEMA 5-20R T-Slot,
accepts15A Plug
(4) NEMA 5-15R
(2) NEMA 5-20R T-Slot,
accepts15A Plug
(1) NEMA L5-30R
Voltage (Normal Mode) 110/120/127 VAC (configurable)
Voltage (Battery Mode) 110/120/127 VAC; ±5% before low-battery warning
Transfer Time 4-6 ms typical
Waveform Sinewave
Battery Parameters
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Ah 4 x 12 x 7.2 4 x 12 x 9 8 x 12 x 7.2 8 x 12 x 9
Recharge Time 5 hours to 90% of rated capacity, after full discharge into resistive load
Battery Backup Time
Full Load 5 minutes
Half Load 10 minutes
Environmental
Operating Temperature, °F (°C) 32 to 104 (0 to 40)
Storage Temperature, °F (°C) 5 to 104 (-15 to 40)
Relative Humidity 0% to 90%, non-condensing
Operating Altitude Up to 10,000 ft (3000m)
Audible Noise <45 dBA
Agency
Safety UL 1778, c-UL Listed
Surge ANSI C62.41 CatA Lev3 (surges) IEC61000-4-5
ESD IEC61000-4-2
Susceptibility IEC61000-4-3
Electrical Fast Transient IEC61000-4-4
Emissions FCC Part 15, Class A
Conducted Immunity IEC61000-4-6
Harmonics IEC61000-3-2
Network surge UL 497 B
Transportation ISTA Procedure 1A Certification
Environmental
ROHS compliant
* NEC limits the input current rating of the PS2200RT3-120XR and PS2200RT3120XRW models to 80% of the input plug's rating. Up to
2200VA/1980W is available by contacting a certified electrician to change the input plug to 30A plug. Emerson Network Power assumes no
liability for damage caused by miswiring or misapplication of the input plug.