Emerson 3U MP2-220N Power Supply User Manual


 
Specifications
11
8.0 SPECIFICATIONS
This 3U POD is intended for use with a UPS meeting all the following requirements:
UPS input cord is compatible with the rating and type of receptacle on the 3U POD labeled “CON-
NECT UPS LINE CORD HERE.”
UPS output receptacle is compatible with the 3U POD input power connector labeled “UPS.”
Available utility is compatible with the 3U POD input connection and an appropriately sized
branch circuit breaker has been provided.
Table 2 Breaker specifications
8.1 Product Warranty Registration
To register for warranty protection:
•Visit the Quick Links section of our Web site at:
http://www.liebert.com
Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
Transfer Time (to and from maintenance bypass) < 6 milliseconds
Operating Ambient Temperature 32°F to 104°F (0°C to +40°C)
Storage Ambient Temperature -4°F to 140°F (-20°C to +60°C)
Dimensions with brackets W x D x H: in. (mm) 19.0 x 5.24 x 5.24 (482.6 x 133 x 133)
Humidity 0 to 95% non-condensing
Agency/Standards UL1778, c-UL, ISTA Procedure 1A
Electrical Rating See Model Label on 3U POD
Model
VA - Volt
Rating
Input Current
Rating
at 208V
Recommended
(Maximum) External
Overcurrent Protection
Recommended Wire
(including ground wire)
(75ºC copper wire)
Maximum Wire
Accepted by
Terminal Block
Terminal
Tightening
Torque
MP2-220N 16A 20A 12 AWG 10 AWG 20 in-lb