1
The Liebert NX is a true on-line, double conversion,
three-phase UPS system that delivers complete,
centralized power protection for mission-critical
systems.
Designed to meet the high availability power needs
of a wide variety of IT applications, the UPS com-
bines a rack form factor, advanced operating fea-
tures and low cost of ownership.
• Increases growth flexibility with Softscale™
technology, plus the ability to parallel modules
for increased capacity and redundancy.
• Achieves higher availability by reducing the
number of UPS units required to power your
data center.
• Reduces total cost of ownership through the use
of longer life batteries and simplified preventive
maintenance.
OUTPUT
Voltage
480VAC, 60Hz,
3-phase, 3-wire plus ground
Voltage
Adjustment
Range
±5%
Voltage
Regulation
1% for balanced load
2% for 100% unbalanced load
Dynamic
Regulation
±5% deviation for 100% load step
±1% for loss or return of AC input
Transient
Response Time
Recover to ±5% of output voltage
within 1/2 cycle
Voltage
Distortion
For linear loads, 1% THD
Less than 4% THD for 100% nonlinear
loads without kVA/kW derating
Phasing
Balance
120° ±0.5° for balanced load
120° ±1° for 100% unbalanced load
Frequency
Regulation
±0.05% single module
±0.25% paralleled modules
Load Power
Factor Range
0.5 lagging to 1.0 without derating
Overload
125% of full load for 10 minutes
150% for one minute, with true
sinusoidal waveform
STANDARDS
Listed to UL 1778 UPS standards, and CSA certified.
Meets current requirements for safe high performance
UPS operation.
LIEBERT
®
NX
™
3-PHASE UPS: 40-120KVA, 60HZ, 480VAC - SITE PLANNING DATA
External Battery Cabinet
Battery
Manufacturer
Battery
Type
Dimensions
in. (mm)
Weight
lb. (kg)
Qty.
Battery
Cabinets
Battery Time (minutes)
40kVA 60kVA 80kVA 100kVA 120kVA
C&D
Technologies
UPS12-100MR
35.3x38.2x78.7
(897x970x2000)
1750
(794)
15————
21795——
UPS12-150MR
2000
(907)
1127———
2 332013 9 7
UPS12-210MR
2500
(1134)
119116——
2 483121 15 11
Enersys HX205
35.3x38.2x78.7
(897x970x2000)
2620
(1188)
119117——
2 462820 15 12
General Specifications
INPUT
Voltage
480VAC, 60Hz
3-phase, 3-wire plus ground
Voltage Range
without derating
+15%, -25%
Frequency Range 57-63Hz
Current
Distortion
3% maximum reflected THD
at full load
Current Limit 140% of full load input current
Current
Walk-In
20 seconds to full load
Programmable, 0 to 30 seconds
Power Factor
>0.99 lagging at full load
>0.98 lagging at half load
Surge
Protection
Sustains input surges without damage,
per criteria listed in IEC 61000-4-5
ENVIRONMENTAL
Operating
Temperature
UPS: 32° to 104°F (0-40°C)
Battery: 68° to 86°F (20-30°C)
Non-Operating
Temperature
-13° to 158°F
(-25° to 70°C)
Relative Humidity 0-95% non-condensing
Operating
Altitude
Up to 6,500 ft. (2,000m)
without derating
Acoustical Noise (full load)
80kVA
<67dB at 80-104°F (27-40°C) ambient
<61dB below 80°F (27°C) ambient
120kVA
<69dB at 80-104°F (27-40°C) ambient
<63dB below 80°F (27°C) ambient