Emerson 6 kVA Power Supply User Manual


 
14
Specifications
Note: Part Numbers GXT2-6000RT208 and GXT2-10000RT208 do not include internal battery kits. When calculating total unit weight, add weight of internal batteries.
LIEBERT GXT2 6 KVA LIEBERT GXT2 10 KVA
Model Number GXT2-6000RT208 GXT2-10000RT208
Model Rating 4200W/5200VA at 127/220 (120 or 240 degrees) 8000W/8660VA at 127/220 (120 or 240 degrees)
4200W/5200VA at 120/208 (120 or 240 degrees) 8000W/8660VA at 120/208 (120 or 240 degrees)
4200W/6000VA at 120/240 (180 degrees) 8000W/10000VA at 120/240 (180 degrees)
4200W/6000VA at 115/230 (180 degrees) 8000W/10000VA at 115/230 (180 degrees)
3780W/5400VA at 110/220 (180 degrees) 7200W/9000VA at 110/220 (180 degrees)
3360W/4800VA at 100/200 (180 degrees) 6400W/8000VA at 100/200 (180 degrees)
DIMENSIONS Unit W x D x H in. (mm) 6.9 x 24.2 x 16.9 (176 x 615 x 430) 10.5 x 26.0 x 16.9 (267 x 660 x 430)
WEIGHT lbs (kg) Unit 67 (30.3) 109 (49.3)
INPUT AC PARAMETERS
Nominal Operating Frequency 50 or 60 Hz (Factory Default = 60)
Factory Default VAC 120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase Angle 120 degrees
Allowable Input Phase Angle 120, 180, 240 degrees, Auto-sensing on application of AC (Restrictions for L-N voltages other than 120 VAC)
Factory Default L1-N, L2-N VAC 120 VAC nominal
Input Frequency w/o Battery Operation 40 - 70 Hz
OUTPUT AC PARAMETERS
Factory Default VAC 120/208 VAC @ 120 degrees
L1-L2 Factory Default Output Phase Angle 120 degrees
Allowable Output Phase Angle 120, 180, 240 degrees Auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC 120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC, ±3%
Frequency 50 Hz or 60 Hz, Nominal
Waveform Sinewave
Overload Rating 200% for 8 cycles; 130% for 10 seconds 200% for 8 cycles then shutdown; 130% for 60 seconds
with transfer to bypass with transfer to bypass
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise <55 dBA, at 1 meter from the rear; <50 dBA, at 1 meter from the front or sides
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Surge Immunity IEEE/ANSI C62.41 Category A & B
Transportation ISTA Procedure 1A
INTERNAL BATTERY
Model Number GXT2-144BATKIT (one required) GXT2-288RTBKIT (two required)
WEIGHT lbs (kg) 79 (35.8) (one required) 78.1 (35.5) (two required)
Type Valve-regulated, non-spillable, flame retardant, lead acid
Quantity x V x Rating 12 x 12V x 9.0 AH (one required) 12 x 12V x 9.0 AH (two required)
Battery Mfg / Part # Yuasa / REW 45-12 FR
Recharge Time 6 Hours to 90% capacity after full discharge into 100% load
OPTIONAL EXTENDED BATTERY CABINET
Model Number GXT2-144VBATT GXT2-288RTVBATT (requires two GXT2-288RTBKIT)
DIMENSIONS W x D x H in.(mm) 3.5 x 24.2 x 16.9 (87 x 618 x 430) 7.0 x 26.0 x 16.9 (178 x 660 x 430)
WEIGHT lbs (kg) Unit 93.6 (42.5) 197.8 (89.9) (Total weight with batteries)
BATTERY PARAMETERS
Typ e Valve-regulated, non-spillable, flame retardant, lead acid
Qty x V x Rating 12 x 12V x 9.0 AH per kit 12 x 12V x 9.0 AH per kit (two required)
Battery Mfg / Part # Yuasa / REW 45-12 FR
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000m) maximum
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Transportation ISTA Procedure 1A
168997_SL23172:15615 govern 7/22/08 2:30 PM Page 15