Configuration
19
7.0 CONFIGURATION
The Liebert GXT2-PP20KRT208 parallel POD allows connecting a maximum of three UPSs in paral-
lel. See the following table for the maximum output power.
7.1 Paralleling for Capacity
When two UPSs are connected to the paralleling system, the maximum output power is 20kVA. Each
UPS supplies 10kVA of output power. Redundant power is not available if either of the paralleled the
UPSs fails.
7.2 Paralleling for Capacity and Redundancy
When three UPSs are connected to the paralleling system, the maximum output power is 20kVA. plus
redundancy of one 10kVA UPS. This setup permits that the paralleling system to operate normally
even if one of the UPSs fails or runs out of battery power.
For the paralleling procedures, see 5.0 - Installation.
Table 2 Maximum output power from paralleled UPSs
Method Number of UPSs Maximum Output Power Redundancy
Paralleling for Capacity 2 20kVA —
Paralleling for Capacity
and Redundancy
3 20kVA 10kVA