38
Table 15 Battery run times
Number of
Batteries/Cabinets
Load Percent
of Capacity
120VAC RT Models
208 VAC RT
Model
500VA 700VA 1000VA 1500VA 2000VA 3000VA 3000VA
Internal Battery
10% 128 105 90 77 77 74 77
20% 826137353336 37
30% 413730232121 21
40% 383223161515 15
50% 342717111111 11
60% 31 22 14 10 8 8 8
70%271811666 6
80%23159555 5
90%20138444 4
100% 17 11 7 4 3 3 3
Internal Battery
+ 1 External
Battery Cabinet
10% 328 306 212 199 183 166 183
20% 209 182 151 133 124 121 123
30% 166 149 123 97 80 79 79
40% 152 130 100 72 41 53 53
50% 139 109 80 41 38 46 45
60% 125 98 68 38 34 39 38
70% 109 81 41 35 30 31 31
80% 100 72 39 32 25 26 26
90% 926337272121 22
100% 79 41 35 23 17 18 18
Internal Battery
+ 2 External
Battery Cabinets
10% 480 373 336 314 311 307 311
20% 334 313 214 188 161 159 160
30% 309 211 166 148 134 133 133
40% 216 185 151 126 105 105 104
50% 197 159 137 103 80 81 80
60% 167 149 122 82 67 68 67
70% 159 139 105 72 40 52 52
80% 152 128 95 62 38 47 47
90% 144 112 80 40 36 43 43
100% 137 104 73 38 33 38 38
Internal Battery
+ 3 External
Battery Cabinets
10% 480 480 480 341 335 332 335
20% 401 341 321 227 206 203 205
30% 338 318 218 185 157 157 157
40% 322 224 191 154 139 139 138
50% 306 205 162 139 120 120 113
60% 219 186 152 123 99 100 100
70% 205 163 141 105 80 81 81
80% 191 155 131 93 70 71 71
90% 167 148 120 79 60 62 62
100% 162 140 106 71 40 51 51