Emerson II TVSS Surge Protector User Manual


 
C
ode
C
ode
C
ode Code Code Code Code Code
S
I
016
160kA
120
120V N 1 Phase L-N 2+W+GND A All N Wire Lugs S E NEMA 4
025
250kA
208
208V
L
1 Phase L-L 2W +GND R Disconnect N Caseless
032
320kA
220
220V
S
Split Phase 3W+GND
040
400kA
230
230V
Y
3 Phase Wye 4W+GND
050
500kA
240
240V
D
3 Phase Delta 3W+GND
060
600kA
277
277V
X 3 Phase Wye 3W+GND
075
750kA
480
480V
H 3 Delta Hi-Leg 4W+GND
100
1000kA
3
Sur
ge
C
onnec
tion A B C D E F Weight
160kA
W
ir
e lu
gs 16 12 9 17.25 9.5 0.44 35
250kA
Dis
c
onnec
t
16 16 9 17.25 10 0.44 45
320kA
W
ir
e lu
g
s 16 12 9 17.25 9.5 0.44 45
500kA Disconnect 16 16 9 17.25 10 0.44 55
600kA Wire lugs 20 16 9 21.25 10 0.44 55
750kA Disconnect 20 20 9 21.25 14 0.44 85
Wire lugs 20 20 9 21.25 14 0.44 85
Disconnect 20 24 9 21.25 18 0.44 95
Interceptor Choose Choose Choose Choose Choose Choose Choose
Series Surge Current Voltage Voltage Modes of Type of Monitoring Enclosure
Rating (L-G) Configuration Protection Connection Option Type
EXAMPLE
SI
0 1
6 1
2 0 Y A R D E
Liebert Interceptor
®
II Surge Suppression 160kA - 1000kA.
System B3 6kv/500A B3/C1 C3
Voltage Mode Ringwave Comb.Wave Comb.Wave Comb.Wave
120/208 L-N 328/344 308/312 376/376 452/536
120/208 L-G 340/348 320/316 364/368 444/584
120/208 L-L 464/448 576/568 680/652 792/832
120/208 N-G 344 284 344 468
277/480 L-N 520/536 532/528 800/800 912/952
277/480 L-G 736/760 688/688 760/776 840/896
277/480 L-L 736/776 720/728 1480/1416 1656/1600
277/480 N-G 736 648 760 896
System Voltage L-N L-G N-G L-L
120/240
330V 400V 400V 600V
120/208
240 N/A 800V N/A 800V
230/400
700V 800V 600V 1200V
277/480
480 N/A 1200V N/A 1500V
*O
the
r mode
s
o
f protection
available; Call
f
ac
t
or
y
.
UL 1449 Clamping Data (Second Edition)
NEMA LS 1 Test Data (without disconnect/with disconnect)
Chart A – Liebert Interceptor
®
II Model Selection
Chart B – Liebert Interceptor
®
II Dimensional Data
1,000kA
How To Specify The Appropriate Model:
All Liebert Interceptor II model numbers begin with the SI prefix. Use Chart A to build your Liebert Interceptor II starting with the Surge Rating column.
Moving left to right, choose the correct configurations from each column for your application. Your completed model number should look similar to the
example below or SI016120YARDE. Refer to Chart B for Liebert Interceptor II dimensional data.
AD
CB
E
F
Standard Monitoring
LEDs, Audible Alarm,
Form C Contacts
C Standard Monitoring
Plus Single Surge
C
o
un
t
e
r
D
S
t
and
ar
d Monitoring
Plus Dual Surge and
Swell Counters
Connection Type Parallel Connected
Agency Listings UL1449, UL1283, cUL, FCC Part 15 Class B
Operating Voltage Range + / - 15%
Fault Current Rating (AIC) 200kAIC
Operating Frequency Range 47 - 63 Hertz
50 ohm EMI/RFI Attenuation 100kHz 41 dB
1MHz 31 dB
10MHz 35 dB
100MHz 53 dB
Protection Modes All applicable modes standard (Line to Neutral, Line
to Ground, Neutral to Ground and Line to Line)
Response Time <0.5 nanoseconds
Temperature -40 to +60 degrees C
Operating Humidity 0% to 95% noncondensing
Status Indication LEDs, Dry Contacts, Audible Alarm
Enclosure NEMA 4 standard
Altitude 0 to 18,000 feet
Audible Noise Less than 45 dBa
Warranty 10-Years Parts and 5-Years On-Site Labor
*Other enclosure
options available;
C
all f