Emerson Network Power.com
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
™
.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation
1050 Dearborn Drive
P.O. Box 29186
Columbus, Ohio 43229
800 877 9222 Phone (U.S. &
Canada Only)
614 888 0246 Phone (Outside U.S.)
614 841 6022 FAX
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
Italy
39 049 9719 111 Phone
39 049 5841 257 FAX
Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 Gloucester Rd, Wanchai
Hong Kong
852 25722201 Phone
852 28029250 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
While every precaution has been taken to ensure accuracy and
completeness in this literature, Liebert Corporation assumes no
responsibility, and disclaims all liability for damages resulting
from use of this information or for any errors or omissions.
© 2008 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
of their respective owners.
® Liebert is a registered trademark of the Liebert Corporation.
SL-23317 (R07/08) Printed in USA
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.
Liebert PSI XR Specifications
Model Number PS1000RT3-120XR PS1500RT3-120XR PS2200RT3-120XR PS3000RT3-120XR
Network Solutions Package Number
PS1000RT3-120XRW PS1500RT3-120XRW PS2200RT3-120XRW PS3000RT3-120XRW
Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W 3000VA/2700W
Dimensions, W x D x H, in (mm)
Unit 17.3 x 19.3 x 3.5
(440 x 490.5 x 88)
17.3 x 19.3 x 3.5
(440 x 490.5 x 88)
17.3 x 27.6 x 3.5
(440 x 700.5 x 88)
17.3 x 27.6 x 3.5
(440 x 700.5 x 88)
Shipping 22 x 24.1 x 9 (560 x 612 x 228) 22 x 24.1 x 9 (560 x 612 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228)
Weight, lb (kg)
Unit 56 (25) 62 (28) 92 (42) 105 (48)
Shipping 64 (29) 70 (32) 101 (46) 115 (52)
Input AC Parameters
Surge Protection 570J
Voltage Range Without Battery
Operation
83 to 159 VAC (configurable)
Frequency Range 45~65Hz, (0.5Hz)
Input Power Cord, 10ft (3m)
attached
NEMA 5-15P plug NEMA 5-15P plug NEMA 5-20P plug NEMA L5-30P plug
Output Receptacles (6) NEMA 5-15R (6) NEMA 5-15R (4) NEMA 5-15R (2) NEMA 5-20R
T-Slot, accepts 15A Plug
(4) NEMA 5-15R (2) NEMA 5-20R
T-Slot, accepts 15A Plug
(1) NEMA L5-30R
Voltage (Normal Mode) 110/120/127 VAC (configurable)
Voltage (Battery Mode) 110/120/127 VAC; 5% before low-battery warning
Transfer Time 4-6 ms typical
Battery Waveform Sinewave
Battery Parameters
Typ e Valve-regulated, non-spillable, lead acid
Recharge Time 5 hours to 90% of rated capacity, after full discharge into resistive load
Battery Backup Time
Full Load 5 minutes
Half Load > 10 minutes. 13-14 minutes typical.
Environmental
Operating Temperature, ˚F (˚C) 32 to 104 (0 to 40)
Storage Temperature, ˚F (˚C) 5 to 104 (-15 to 40)
Relative Humidity 0% to 90%, non-condensing
Operating Altitude Up to 3000m (10,000 ft) at 35˚C (95˚F) without derating
Audible Noise <40 dBA, internal fan(s) Off; <45 dBA, internal fan(s) On
Agency
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class A
Network Surge UL 497 B
Transportation ISTA Procedure 1A Certification
Rail Kit (included)
Rail Kit RAILKITPS3G-AEC
Battery cabinet specifications
Model Number PSRT3-24VBXR PSRT3-48VBXR
Used w/UPS Model PS1000RT3-120XR, PS1500RT3-120XR PS2200RT3-120XR, PS3000RT3-120XR
Dimensions, W x D x H, in (mm)
Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
Shipping 22 x 26.6 x 9 (560 x 675 x 228)
Weight, lb (kg)
Unit 64 (29)
Shipping 73 (33)
Batteries
Typ e Valve-regulated, nonspillable, lead acid
Manufacturer CSB, YUASA or Equivalent
Environmental
Operating Temperature, ˚F (˚C) 32 to 104 (0 to 40)
Storage Temperature, ˚F (˚C) 5 to 104 (-15 to 40)
Relative Humidity 0% to 90%, non-condensing
Maximum Operating Altitude 10,000 ft. (3000m) at 95˚F (35˚C) without derating
Agency
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class A
Transportation ISTA Procedure 1A Certification
NEC limits the input current rating of the 2200VA model to 80% of the input plug’s rating. If 1920 or more is required, contact a certified electrician to change the input plug to
30A plug. Emerson Network Power assumes no liability for damage caused by miswiring or misapplication of the input plug.