INSTALLATION (continued)
1 --- 4
observe these lights
Figure 1–5. St andard controls and indicators.
2–VoltageChecks
First check nameplate on transfer switch; rated voltage
mustbethesameasnormalandemergencylinevoltages.
Verify that the feeders have been
connected to the proper lugs.
Use extreme caution when using a met er
to measure voltages in the following
steps. Do not touch power terminals;
sh oc k , burns , or d e at h could result !
Performsteps 1through 6at the right. Observe the status
lights. See Figure 1–5.
● Black circle means light is on.
❍ White circle means light is off.
* If necessary, adjust voltage regulator on the generator
according to the manufacturer’s recommendations. The
Automatic Transfer Switch will respond only to the rated
voltage specified on the Transfer Switch nameplate.
1
Close the normal source circuit
breaker. The Normal Transfer
Switch Position and the Normal
Source Accepted lights should
come on.
Source Accepted
Normal
Emergency
2
Use an accurate voltmeter to
check phase to phase and
phase to neutral voltages pres -
entatthetransferswitchnormal
source terminals.
3
Close the emergency source
circuit breaker. (Start generator,
if necessary.) The Emergency
Source Accepted light should
come on.
Source Accepted
Normal
Emergency
4
Use an accurate voltmeter to
check phase to phase and
phase to neutral voltages pres -
ent a t t he transfer switch emer-
gency source terminals.*
5
Useaphaserotationmeterto
check phase rotation of emer-
gency source; it must be the
same
as the normal source.
A
B
C
6
Shut down the engine–genera-
tor, if applicable. The Emergen -
cy Source Accepted light should
go off. Then put the starting
control selector sw itch (on the
generator set) in the automatic
position. Close enclosure door.
Source Accepted
Normal
Emergency
Now continue to 3 – Electrical Operation on next page.