Typical NEMA LS1 Data
Type 1 Unit; Type 2 Unit;
Line - Neutral Line - Neutral
120/208V & 120/240V 120/208V & 120/240V
C
lamping Voltage (Vpk) Clamping Voltage (Vpk)
Category A Ringwave 176 284
(6 kV / 0.2 kA)
Category B Ringwave 288 304
(6 kV / 0.5 kA)
UL 1449 Combination Wave 256 300
(6 kV / 0.5 kA)
Category B Combination 304 336
W
a
v
e (6 kV / 3.0 kA)
Category C Combination 440 408
Wave (20 kV / 10.0 kA)
Whi
l
e e
v
e
r
y precaution has been taken to ensure accuracy and
c
om
pl
e
t
e
ne
s
s in this lit
erature, Liebert Corporation assumes no
r
esponsibility, and disclaims all liability for damages resulting
f
r
om u
s
e o
f this information or for any errors or omissions.
© 2007 Liebert Corporation. All rights reserved throughout
the world. Specifications subject to change without notice.
All names referred to are trademarks or registered trademarks
o
f their respective owners.
® Liebert and the Liebert logo are registered trademarks
of the Liebert Corporation.
SL-22090 (R05/07) Printed in USA
B
usiness-Critical Continuity
, Eme
rson Network
P
o
w
e
r an
d the Eme
rson Network Power logo are
trademarks and service marks of Emerson
Electric Co. ©2007 Emerson Electric Co.
Emerson Network Power.com
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
.
AC Power
Connectivity
DC Power
Embedded Computing
Embedded Power
Monitoring
Outside Plant
Power Switching & Controls
Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection
Liebert Corporation
1050
Dearborn Drive
P.O.
Box 29186
Col
umbus, Ohio 43229
800 877 9222
Phone (U.S. &
Canada Onl
y)
614 888 0246
Phone (Outside U.S.)
614 841 6022
FAX
Via
Leonardo Da Vinci 8
Zona
Industriale Tognana
35028
Piove Di Sacco (PD)
Ital
y
39 049 971
9 111 Phone
39 049 584
1 257 FAX
Emerson Network Power Asia Pacific
7/F., Dah Sing Financial Centre
108 G
loucester Rd, Wanchai
Hong
Kong
852 25722201 Phone
852 28029250 FAX
liebert.com
Technical Support
800 288 6169 Toll-Free
607 724 2484 Phone
607 722 8713 Fax
Liebert TYPE SS Transient Voltage Surge Suppression
MOV/SAD Current Sharing – Type 1 Model
The Liebert Answer:
The Liebert TYPE SS Type I Model
offers a true, coordinated multi-stage
system of suppression. It integrates
the fast response time of the silicon
avalanche diode (SAD) with the high-
energy capability of the metal oxide
varistor (MOV) for increased reliability
and performance. This unique circuitry
does not sacrifice the sensitive SAD
module when subjected to a
damaging high-energy transient event.
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0
0 5000 10000 15000 20000 25000 300
00
8/20 µs Surge Current (Amperes)
Surge Current (%)
SAD Module
MOV Module
Technical Specifications
Voltage Configurations 120/240V and 120/208V
(P
lease consult factory for additional voltage configurations)
Maximum Continuous ≥125%
Operating Voltage (MCOV)
Fault Current Rating (AIC) 200 kAIC
Operating Frequency Range 47 – 63 Hz
Connection Parallel (4-6 AWG recommended and 14-1/0 AWG capable); wire lug or disconnect
Modes of Protection Line to Neutral/standard
Surge Current Capacity 160 kA per mode
Response Time <0.5 nanoseconds
Dimensions 15.32 in. x 13.32 in. x 6.60 in.
Weight 35 lbs.
Operating Temperature -40°C to +60°C
Status Indication LEDs, Form “C” contacts — 2 sets
Form “C” Contact Rating 120 VAC, 5.0 amps, pF of 1.0
Certifications Product performance and safety standards — UL 1283, UL 1449 Second Edition 2005,
(effective Feb. 9, 2007), C22.2 No.8 Bulletin 516, NEMA LS1-1992
T
ec
hnology Type 1 Hybrid TVSS — 20 kA of SAD protection and 160 kA of MOV protection
Type 2 MOV only TVSS — 160 kA of MOV protection
Enc
lo
sur
e NEMA 4X; suitable for indoor or outdoor applications
Warranty Covered 24x7 by Emerson Network Power Service Business 10-Years Parts and 5-Years
On-Site Labor