Emerson WEB/485 Network Hardware User Manual


 
Liebert
®
IntelliSlot
®
Web/485 Card
With Adapter
Quick Start Guide
INSTALL
Locate the adapter mounting location within your Liebert
equipment.
Secure the card with the supplied screws.
Connect the equipment’s communication cable to the TB1 terminal
block or P1 on the card (See equipment user manual for details).
Connect an Ethernet cable to RJ45.
Connect a Modbus (RS-485) cable to the TB2 terminal block.
Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal
block; Pin 1 is at the far left, and Pin 2 is the middle pin.
DHCP: The card ships with DHCP service enabled. The MAC address is
printed on a sticker affixed to the top of the card.
OR
Static IP: To assign a static IP address, use the Service Terminal to con-
figure the card. Proceed to Steps 2 & 3.
CONNECT THE CABLE
Connect a configuration cable (null modem) to the DB-9 port
on the card and to a COM port on your PC. The configuration
cable is available separately from Emerson (P/N LIEBNULL).
CONFIGURE THE CARD
Use terminal emulation software,
such as HyperTerminal
, to open a
direct connection to the card.
•Press Enter for the Main Menu.
Select option 2 and follow the instructions to
enter an IP ADDRESS, NETMASK and
GATEWAY.
•Press Esc to return to the Main Menu.
Enter X to save your changes and reboot the card.
TB2
(P1: +)
(P2: -);
P1 is at
the right side
of terminal block.
Network Port
for NMS and
Web Access
TB3
(P1: +)
(P2: -)
(P3: NC)
P1 is on the
left end of
terminal
block.
DB-9
Port
MAC Address
P1
TB1 (P1: +; P2: -); P1 is at
the right side of terminal block.
Terminal Emulation
Software Configuration
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None