Falcon SG2K-2TXI Power Supply User Manual


 
SG Series
TM
UPS PLUS
®
800VA to 1.5kVA
Model Number SG800-1T SG1K-1T SG1K-2T SG1.5K-1T
Nominal VA 800 1000 1000 1500
Electrical Input
Nominal AC Voltage 120V 120V 230V 120V
AC Voltage Range 87-140V 87-140V 170-275V 87-140V
Current-Amps 5.5 6.9 3.6 10.7
Frequency 50/60 Hz
±
5% (Auto Tracking)
Power Factor Correction > 0.95
Efficiency (Typical) > 86%
Electrical Output
Watts 560 700 700 1050
AC Voltage
(Switchable)
100V
110V
115V
120V
100V
110V
115V
120V
200V
220V
230V
240V
100V
110V
115V
120V
Frequency 50/60 Hz (Auto Tracking)
Frequency Stability
±
0.3% (Battery Mode)
Voltage Regulation
±
2%
Step Load Change
±
7% for 100% load variation
Harmonic Distortion < 3% Linear Load, < 5% Non-Linear Load
Overload 105% load for 50 Seconds
Crest Ratio 3:1
Battery
DC Voltage 36V 72V
Type 12V, 7AH Sealed Lead Acid Maintenance-Free
Back Up Time @ Full Load
@ 1/2 Load
9 Minutes
25 Minutes
6 Minutes
19 Minutes
11 Minutes
30 Minutes
Recharge Time 8 Hours to 90%
Battery times are approximate.
Transfer Time
Line Fails/Recovers Zero
UPS to Bypass or Reverse < 4ms
After Overload Auto Transfer to UPS
Electrical Connections
Input 6’ Cord with
5-15P
6’ Cord with
5-15P
6’ Cord with
Schuko or 6-15P
6’ Cord with
5-15P
Output (6) 5-15R (6) 5-15R (4) IEC 320 (6) 5-15R
Contact the factory for other input/output options.
Environmental
Operating Temperature 0º C - 40º C (32º F to 104º F)
Humidity 10% to 95% Non Condensing
Altitude 7,000 Feet
Cooling Low Velocity Forced Air Fans
Audible Noise @ 1 Meter <45dBA < 50dBA
Controls and Indicators
LED Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level
Audible Alarms DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault Alarm
Communications RS-232 Serial Port (Bundled UPSilon 2000 Software)
Mechanical
Dimensions H x W x D inches
(mm)
8.7 x 6.0 x 15.8
(220.9 x 152.4 x 401.3)
13.8 x 7.6 x 18.9
(350.5 x 193.0 x 480.0)
Weight lb. (kg) 33 (14.9) 68 (30.9)
Agency Listing UL 1778, CUL,
FCC Class A
CE
available with Schuko
plug only
UL 1778, CUL,
FCC Class A
Available Options
Option A 60 Hz to 50 Hz Frequency Conversion
Option B 50 Hz to 60 Hz Frequency Conversion
Option C SNMP/HTTP Network Card (Internal)
Option D Standard Contact Closure Interface Card
Maintenance Bypass Make-Before-Break External Wrap Around
External Battery Packs Extended Run Time Battery Packs (minutes to hours)
Fast Battery Charger Fast Charger internal to the Extended Battery Pack Cabinet (Required for battery times 2 hours or more.)
22