Falcon SG3K-2T-HW Power Supply User Manual


 
1.1 UPS Output Requirements
Note: The outputs of the SG2K-2T-HW & SG3K-2T-HW hardwire models are not
configured for 240/120Vac split-phase operation. Should a 240/120Vac
split-phase output configuration be required, please contact the factory.
MODEL RECOMMENDED
BRANCH RATED OUTPUT
CIRCUIT
BREAKER
SG2K-1T
-HW:
Output 1: 100, 110, 115 or 120Vac selectable, 1 phase, 2 wire plus ground 20A
SG2K-2T-HW
Output 1: 200, 220, 230 or 240Vac selectable, 1 phase, 2 wire plus ground 15A
SG3K-1T-HW
Output 1: 100, 110, 115 or 120Vac selectable, 1 phase, 2 wire plus ground 30A
SG2K-2T-HW
Output 1: 200, 220, 230 or 240Vac selectable, 1 phase, 2 wire plus ground 20A
1 2 3 4 5
View of the Input/Output Hardwire Terminal Block
This terminal block is located on the UPS rear panel and shown with the access cover plates
removed.
Use only the lower terminals and wire securing screws when making wiring connections to
the UPS.
DO
NOT USE THE UPPER TERMINAL CONNECTIONS
Refer to the Wire Gauge Table on Page 7 for recommended wire sizes.
Refer to the Torque Specification Table on Page 7 and tighten all 20 screws as specified.
Refer to Pages 9-10 for the terminal wiring designations for your specific SG UPS model.
Terminal Wiring Designations
1 - Utility L1 4. UPS Output L1
2 - Utility L2 or Neutral 5. UPS Output L2 or Neutral
3 - Input and Output Grounds
7