Falcon SG6K-1TX Power Supply User Manual


 
15
Typical SG5 & 6kVA Rear Panel Layout
(Shown with Power Distribution Center )
Output Voltage & Green Mode
Select Switches
RS-232 Computer Interface
Connector
Communications Option Slot
Cover Plate
COOLINGFANS
DO NOTBLOCK AIR FLOW
INPUT AC CIRCUIT BREAKER
ALWAYS TURN ON AFTER THE
BATTERY CIRCUITBREAKER
HAS BEEN TURNED ON
BATTERY CIRCUIT BREAKER &
DISCONNECT
VERIFY THIS DISCONNECT IS IN
THE OFF POSITION WHEN:
* The UPS is being installed.
* The UPS is to be turned off or
stored for more than five days.
* Connecting external battery banks.
* Servicing the UPS.
WARNING
NEVER TURN OFF THIS
DISCONNECT WHILE THE UPSIS
OPERATING FROM UTILITY.
POWER OR DAMAGE MAY RESULT.
ALWAYS TURN OFFTHE UPS
FIRST.
OUTPUT POWERDISTRIBUTION
CENTER
(see page 14)
MAINTENANCE BYPASS
SWITCH
REFER TO PAGE 20 FOR
OPERATINGINSTRUCTIONS
WARNING
NEVER TURN THIS SWITCH TO
THE ON POSITION UNLESS THE
UPS HAS BEEN PLACED INTO
MANUAL BYPASS, OR THE UPS
HAS BEEN TURNED OFF
IMPORTANT
TO TURN OFF THE UPS
SWITCH THE INPUT CIRCUIT BREAKER LOCATED ON THE UPS REAR PANEL TO THE “OFF” POSITION
AND PRESS THE ON/OFF BUTTON LOCATED ON THE UPS FRONT PANEL UNTIL THE UPS BEEPS. THE
UPS WILL RUN FOR ABOUT 30 SECONDS AND SHUT DOWN. DO NOT PRESS THE ON/OFF BUTTON
OR TURN THE CIRCUIT BREAKER ON AGAIN DURING THE SHUTDOWN PROCESS OR THE UPS WILL
GO TO AN ALARM CONDITION, WARNING THAT THE UPS WAS NOT SHUT DOWN PROPERLY. SHOULD
THIS OCCUR, TURN OFF THE INPUT CIRCUIT BREAKER AGAIN AND WAIT UNTIL THE UPS SHUTS
DOWN.