Falcon SG6K-2TC Power Supply User Manual


 
2.0. UPS Output Requirements
Note: The outputs of SG 5 & 6kVA models are not configured for 208 or 240Vac
split-phase operation. Please reference the output configuration diagrams on pages
9-10 prior to making any wiring connections to the UPS. Should a 208 or 240Vac
split-phase output configuration be required, please contact the factory.
MODEL RECOMMENDED OUTPUT
CIRCUIT BREAKER
SG5K-1TX:
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A
Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) 50A
SG5K-2T
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A
Output 2: None
SG5K-2TX
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A
Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) 50A
SG6K-1TX
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A
Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) 50A
SG6K-2T
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A
Output 2: None
SG6K-2TX
Output 1: 208, 220, 230 or 240Vac selectable, 1 phase, 2 wire 30A
Output 2: 115, 120, 125 or 130Vac, 1 phase, 3 wire (follows output 1) 50A
IMPORTANT
OUTPUT REQUIREMENTS
8
View of the Input/Output Hardwire Terminal Block
This terminal block is located on the UPS rear panel and shown with the conduit mounting and
access cover plates removed.
Use only the lower terminals and wire securing screws when making wiring connections to
the UPS.
DO NOT USE THE UPPER TERMINAL CONNECTIONS
Refer to the Wire Gauge Table on Page 7 for recommended wire sizes.
Refer to the Torque Specification Table on Page 7 and tighten all 20 screws as specified.
Refer to Pages 9-10 for the terminal wiring designations for your specific SG UPS model.
Terminal Designation Numbers
1 2 3 4 5 6 7 8 9 10