SG2K-2TXI & SG3K-2TX
Typical Rear Panel Overview
COVER PLATE FOR
COMMUNICATIONS
SLOT
EXTERNAL BATTERY
CONNECTOR COVER
PLATE
OUTPUT FUSE
S
FOR
THE TOP RECEPTACLE
208
-
240Vac OUTPUT
RECEPTCALE
120
Vac
OUTPUT
RECEPTACLE
LINE CORD INLET
MAIN POWER SWITCH
&
INPUT CIRCUIT
BREAAKER
COOLING FANS
DO NO BLOCK
RS
-
232
CONNECTOR
DIP SWITCHES
SG2K-2TXI Output Configuration
The SG2TXI model provides three galvanically isolated 240Vac and 120Vac outputs. The
two 120Vac receptacles are derived split phase from the isolated, center tapped 240Vac
output. The center tap has been grounded to provide a derived neutral for both 120Vac
outlets. Due to this, the 120V load is divided between the two 120Vac receptacles. The
combined load on all outputs must never exceed 1400 wats.
SG3K-2TX Output Configuration
The SG3K-2TX model provides galvanic isolation only on the 120Vac outlets. The 120Vac
outlets have been limited to a 1400 watt maximum output. The 208-240Vac output is
derived directly from the UPS inverter, which is not isolated. The combined load on all
outputs must never exceed 2100 watts.
BREAKER
MAIN POWER SWITCH &
INPUT CIRCUIT BREAKER
120Vac OUTPUT
RECEPTACLES
OUTPUT FUSES
(2) PLACES
208-240Vac
RECEPTACLE