Appendix A. Driver Notes
Appendix A.1. Continuous Map Descriptors
RS View has been known to crash if it tries to read a Server mapping that is discontinuous.
e.g. Server map 1: N21: 0-31
Server map 2: N21: 32-100
This will panic the FieldServer and crash RS view as the DF1 will attempt to map N21: 0-100
If set up as:
Server Map 1: N21: 0-100 No problems are experienced
Appendix A.2. Checksum
You can now specify a checksum parameter for the serial connection.
The heading keyword is "Checksum" and the possible values are
1) BCC or 2) CRC-16
If nothing is specified it defaults to BCC.
Example:
Connections
Port, Baud, Protocol, Checksum
P1, 9600, DF1_FD, CRC-16
The Checksum is valid for both DF1_FD and DF1_HD.
Appendix A.3. Command Support
The following commands are supported by the FieldServer for the various PLC types:
PLC_Type File_Type FNC Read FNC
Write
Typical
Command
N 1 Range Read 0 Range Write N7: 3, L5
F 1 Range Read 0 Range Write F12: 3, L5
PLC3
B 1 Range Read 2 Bit Write B3/4: 5, l5
N 1 Range Read 0 Range Write N7: 3 , L5
F 1 Range Read 67 Typed Write F12: 3, L5
PLC5
B 1 Range Read 26 Read Modify Write B3/4: 5, L5
N A2/A1
Protected Typed
Logical Read
AA
Protected Typed
Logical Write
N7: 3, L5
F A2/A1
Protected Typed
Logical Read
AA
Protected Typed
Logical Write
B3/4: 5, L7
B A2/A1
Protected Typed
Logical Read
AB
Protected Typed
Logical Write
B3/4: 5, L8
I A2/A1
Protected Typed
Logical Read
- - I: 13, L5
SLC5
O A2/A1
Protected Typed
Logical Read
- - O: 13, L5