FieldServer FS-8700-128 Server User Manual


 
FS-8700-128 Safetran SCS-128 Manual Page 7 of 15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
4.2. Client Side Connection Descriptions
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is connected
to the FieldServer
P1-P8
1
Protocol Specify protocol used
SCS-128
SCS128
Safetran SCS-128
Baud* Specify baud rate
75, 150, 300 ,600, 1200, 2400, 9600
(Vendor limitation)
Parity* Specify parity
Even (Vendor limitation)
Data_Bits* Specify data bits
8 (Vendor limitation)
Stop_Bits* Specify stop bits
1 (Vendor limitation)
Handshaking*
Specify hardware handshaking
None
Poll_Delay* Time between internal polls
0-32000 seconds, 0.05 seconds
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking, Poll_Delay
P8, SCS-128, 9600, Even, None, 0.100s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for Node
Up to 32 alphanumeric
characters
Node_ID SCS-128 station address of physical Server Node 1-127
Protocol Specify protocol used
SCS-128
SCS128
Safetran SCS-128
Connection
Specify which port the device is connected to the
FieldServer
P1-P8
1
SCS128_Ack*
If ON, Ack will be sent to Server upon receipt of every
indication response
OFF, ON
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Connection, SCS128_Ack
NODE_A, 1, SCS-128, P8, OFF
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.