FieldServer FS-8700-15 Computer Drive User Manual


 
FS-8700-15 Modbus Daniels Manual Page 4 of 7
device is connected to the
FieldServer
FS-X20 Serves: Serial Port
Protocol Specify protocol used Modbus_Daniels
Baud* Specify baud rate
110 – 115200, standard baud
rates only, 9600
Parity* Specify parity
Even, Odd, None, Mark,
Space
Data_Bits* Specify data bits 7, 8
Stop_Bits* Specify stop bits
1
Handshaking*
Specify hardware
handshaking
RTS, RTS/CTS, None
Poll _Delay* Time between internal polls 0-32000 seconds, 1 second
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking, Poll_Delay
P1, Modbus_Daniels, 9600, Even, None, 0.100s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Node_ID
Modbus station address of
physical server node
1-255
Protocol Specify protocol used Modbus_Daniels
Connection
Specify which port the device is
connected to the FieldServer
FS-X40 Serves: P1-P8, R1-R2
FS-X20 Serves: Serial Port
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Connection
PLC 1, 1, Modbus_Daniels, P1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com