4. Configuring the FieldServer as a DeviceNet Slave
For a detailed discussion on FieldServer configuration, please refer to the FieldServer
Configuration Manual. The information that follows describes how to expand upon the factory
defaults provided in the configuration files included with the FieldServer (See “.csv” files
provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer
to communicate with a DeviceNet Master/Scanner.
The configuration file tells the FieldServer about its interfaces, and the routing of data required.
In order to enable the FieldServer for DeviceNet communications, the driver independent
FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual
node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to
the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to
do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the
default.
4.1. DeviceNet Settings
Section Title
FieldServer
Column Title Function Legal Values
System_Station_Address* DeviceNet MAC ID of the FieldServer 0-63
Note
:
The DeviceNet MAC ID can also be set via the DIP switches on the side of the FieldServer
but then the system station address parameter must be removed from the configuration file.
Refer to Appendix B.1 for more information.
Example
// FieldServer
FieldServer
Title, System_Station_Address
DeviceNet_Test, 5