FieldServer FS-8700-23 Computer Drive User Manual


 
FS
-
8700
-
23 Cleaver Brooks Hawk Driver Manual
Page
8
of
13
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
4.4. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric characters
CB Link_ID Device address
See Section 4.4.1 A, B, and C
below
Protocol Specify protocol used CB_Link
Port Port connection R1-R2
Node_Type
Specify controller connected to CB-
Link
See Section 4.4.2
Example
// Client Side Nodes
Nodes
Node_Name, CBlink_ID, Protocol, Port, Node_Type
CBH1, 0 1 20, CB_Link, R2, Hawk
4.4.1. Node_ID
Format for declaring node ID is A B C.
A: 0 if only one CB-Link is attached, 8–254 if multiple CB-Links are attached, Default = 0
B: Slot the device is attached to in the PC Link 1-5, default 1
C: Device type (Declare Device Type Code):
Device Description Device Type Code
Auxenh 26
Ec78xx 32
Efenh 26
Hawk 20
Llenh 26
Orenh 26
Pulsa 19
Q7700 1
Qm40xx 17
Rm78xx 32
S7800 36
S7830 34
Tdenh 26
Testcard 99
Trapscan 18
4.4.2. Node_Type
Hawk, EC78XX. Others by request. (Refer to Device Information Table)