A SERVICE OF

logo

FS-8700-54 MDA CM4 Driver Manual
FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042
Visit our website: www.fieldserver.com E-mail: support@fieldserver.com
Page 3
2.2.2 Client Side Connections
Section Title
Connections
Column Title Function Legal Values
Port Specify which port the device is
connected to the FieldServer
P1-P8, R1-R2
Baud * Specify baud rate 300-9600-38400
Parity * Specify parity Even, Odd, None
Data_Bits * Specify data bits 7, 8
Stop_Bits * Specify stop bits 1, 2
Handshaking * Specify hardware handshaking RTS, RTS/CTS, None
Example:
// Client Side Connections
//
Connections
Port, Baud, Parity, Data_Bits, Stop_Bits, Protocol
P8, 9600, None, 8, 1, CM4
2.2.3 Client Side Nodes
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Up to 32 alphanumeric characters
Node_ID Node ID of physical server node
(PLC or Slave Device)
1-255
Protocol Specify protocol used Modbus/TCP, Modbus RTU, etc
Example:
// Client Side Nodes
//
Nodes
Node_Name, Node_ID, Protocol, Connection
CN_CM4_1, 1, CM4, P8