FieldServer FS-8700-87 Computer Drive User Manual


 
FS
-
8700
-
87 SDD16 Driver Manual
Page
7
of
10
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
4.2. Client Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is
connected to the FieldServer
R1-R2
FSx40 Servers
FSx20 Servers
Baud Specify baud rate 1200, 2400, 4800, 9600
Parity* Specify parity
None
Data_Bits*
Specify data bits
8
Stop_Bits*
Specify stop bits
1
Protocol
Specify protocol used SDD16
Handshaking* Specify hardware handshaking
None
Line_Drive_On Time to wait before driving line 0.001s
Line_Drive_Off
Time to wait before releasing
line
0s
Poll _Delay*
Time between internal polls
0-32000 seconds,1 second
Example
// Client Side Connections
Connections
Port, Baud, Parity,
Protocol, Handshaking,
Poll_Delay, Line_Drive_On, Line_Drive_Off
R1, 9600, None, SDD16, None, 0.100s, 0.001s, 0s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node
Up to 32 alphanumeric
characters
Node_ID Module address
0-255 (48 is default address
on module)
Protocol Specify protocol used SDD16
Port
Specify which port the device
is connected to the
FieldServer
R1-R2
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Port
Module_1, 48, SDD16, R1