4.4.47. Map Descriptor Example 44 - use keypad = Boolean
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Cmd, Length
Use_Keypad, Use_Keypad, 0, wrbx, SYSPLUS_01, Use_Keypad, 1
A Boolean value of 1 for “true” or 0 for “false” must be written to Data_Array_Name at Data_Array_Offset to trigger this command.
4.4.48. Map Descriptor Example 45 - edit program program_num
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Cmd, Length
Ed_Program, Ed_Program, 0, wrbx, SYSPLUS_01, Ed_Program, 1
A program_num value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.
4.4.49. Map Descriptor Example 46 - edit step step_num
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Cmd, Length
Ed_Step, Ed_Step, 0, wrbx, SYSPLUS_01, Ed_Step, 1
A step_num value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.
4.4.50. Map Descriptor Example 47 - edit analog channel
// Client Side Mao Descriptors
Map Descriptor
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, SysPlus_Cmd, Length
Ed_Analog, Ed_Analog, 0, wrbx, SYSPLUS_01, Ed_Analog, 1
A channel value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.