FieldServer FS-8700-97 Computer Drive User Manual


 
FS-8700-97_Lutron_Machine Manual Page 10 of 11
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Column Title Function Legal Values
area_status
sys_var_val_bin
sys_var_val
Zone Machine:
run_script_AB
zone_intensity
fade_zone
run_script_multi
zone_intensity
sys_var_val_bin
sys_var_val
DA_Lut_List
Name of Data Array that contains a
list of parameters needed to
execute the command.
A Data Array name.
DA_Lut_List_Offset
The offset into the DA_Lut_List
Data Array from where the list data
is to be used.
0 to the maximum offset
into the DA_Lut_List
Data Array.
DA_Lut_Parms
Name of Data Array that contains
parameters needed to execute the
command.
A Data Array name.
DA_Lut_Parms_Offset
The offset into the DA_Lut_Parms
Data Array where the driver will
retrieve the parameters.
0 to the maximum offset
into the DA_Lut_Parms
Data Array.
Area GRAFIK system area number 0 – 511
Sys_var GRAFIK system variable number 0 – 65535
Zone GRAFIK system zone number 0 – 511
Length
Length of Map Descriptor. The
length is an indication of the
number of data elements this Map
Descriptor is responsible for
updating. It is used in the overall
points calculation of the
FieldServer.
See example Map
Descriptors for individual
lengths per Map
Descriptor.
Multi_Scripts_Length
The length of the Data Array
specified under DA_Lut_List when
used with Grafik command:
run_script_multi
1 – 10,000
4.4.3. Timing Parameters
Column Title Function Legal Values
Scan_Interval
Rate at which data is
polled
0.001s