FieldServer FS-8707-06 Computer Drive User Manual


 
FS
-
8707
-
06 FST OPC Server for FieldServers
Page
9
of
15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
7. Quick Start Steps to Implement a Simple Intellution Fix Configuration
1. Configure a FieldServer with a valid IP address. Make sure that at least one Data Array
exists. An N1 or N2 connection must be configured with the SMT protocol (SMT is default
so the protocol field can be blank). This Nx connection must be the one used to connect to
the OPC Server machine.
2. Open a DOS box and “PING” the FieldServer from this machine to check that the networking
is correctly set up.
3. Configure Data Arrays in the FieldServer & note their names and data types (Read
FieldServer Configuration Manual for more info)
4. Run the “FST Configurator” (This is in the Start menu prrogram group you selected when
you installed the OPC Server), and add an Ethernet connection to the config tree
5. Add a FieldServer to the config tree, edit the IP address & change the default name to
something meaningful (note for future steps)
6. Add a Data Array to the config tree
Set the Name to that used inside the FieldServer. The name is not case sensitive and will
be forced to uppercase.
The default “offset” is 0, and you will use this in 99 % of cases.
Set the length to the number of elements in the FieldServer/Data Array or less. The
maximum length is limited to 500. If you require more, make another poll block with offset
500
Set the data storage type to the data type of the Data Array in the FieldServer (this is
important, as you may get incorrect values if set incorrectly)
7. Press the green “Start” button
8. Press the “Stats” button & check that we are sending & receiving, if not re-check the names
of the Data Arrays, the IP address of the FieldServer. Keep your first configuration as
simple as possible, one Data Array only.
9. Now go to the Options | Setup menu & set the default path to filename - <fix node name>
& path = \FIX32\PDB or \Dynamics\PDB
10. Now Save the configuration to this location, It is not necessary to save every time you
make a change. Fix simply requires this file to exist on disk.