FieldServer HCS-R Computer Drive User Manual


 
FS-8700-127 Hanning & Kahl HCS-R Manual Page 7 of 17
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
4.2. Client Side Connection Descriptions
Section Title
Connections
Column Title Function Legal Values
Port
Specify which port the device is
connected to the FieldServer
P1-P8
1
Protocol Specify protocol used
HCS-R
HCSR
H&K HCS-R
Baud* Specify baud rate
9600 (Vendor limitation)
Parity* Specify parity
None (Vendor limitation)
Data_Bits* Specify data bits
8 (Vendor limitation)
Stop_Bits* Specify stop bits
1 (Vendor limitation)
Handshaking* Specify hardware handshaking
None (Vendor limitation)
Poll_Delay* Time between internal polls
0-32000 seconds, 0.05 seconds
Example
// Client Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking, Poll_Delay
P8, HCS-R, 9600, None, None, 0.100s
4.3. Client Side Node Descriptors
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for Node Up to 32 alphanumeric characters
Node_ID
HCS-R station address of physical
server Node
240 (Protocol limit)
Protocol Specify protocol used
HCS-R
HCSR
H&K HCS-R
Connection
Specify which port the device is
connected to the FieldServer
P1-P8
1
Example
// Client Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Connection
PLC 1, 240, HCS-R, P8
1