GD Commerce EDA-M100 Computer Hardware User Manual


 
GD Systems
Page - 5 Windmill
Device Type The device type of the unit installed. To ensure correct operation this value must be correct.
The codes follow the product code. If you are unsure then the ‘X’ option must be used. Zone
The zone number must be programmed between the following values
EDA-M100 system 1 – 999 zones
EDA-M200 system 1-20 zones
Locations Text The device location text can be set using a maximum of 37 characters
Day/Night Mode On If analogue devices are being used (500 and 600 range of detectors) then for individ-
ual units the day night mode can be selected. In the global options the start and end time of this mode
can be selected and the sensitivity changed during these hours can be selected.
Sensitivity If analogue devices have been fitted *500 and 600 range of detectors) then the sensitivity can be
selected. The default is ‘Normal’ but if a higher sensitivity is required for computer rooms or high risk areas
the sensitivity should be set higher. If devices are fitted in hostile areas or roof voids then the lower
sensitivity should be set.
2nd Input Used If the 2nd input is being used this check box must be selected to allow a unit number to be
entered.
2nd Input Device Number If the 2nd input is used a device number must be assigned. This will be the de-
vice number displayed on the panel should the 2nd input detect an alarm condition. If not defined it will de-
fault to the next unit number provided the panel is put into the self learn mode. To ensure this operates
correctly the unit should always be assigned if being used.
Save and Exit To return to the previous screen this button must be pressed.
Once changes are made they are automatically saved and can only be changed back by re-typing the older
values.
5.4.2 Change Device Cause and Effects
If the cause and effects for a particular device need to be changed position the scroll bar to detail the ap-
propriate unit number and double click on the column labelled ‘Special’ for the particular device. Screen 5.4
will be displayed. The cause and effects are listed in the following section.
If the device number is not correct then the up and down arrows can be used to reposition the device
number. It should be noted that any changes made prior to changing the device number will automatically
be saved.