GE 350 Power Supply User Manual


 
OPM_MLE_LTE_350_1K0_1GB_V011 9 DE ML Series: user manual 1.1 (GB)
GE Digital Energy
ML Serie
s
g
ML Series model : 350 500 700 1000
Ratings
Voltage Amperes (VA) / Watts (W) : 350 / 210 500 / 300 700 / 420 1000 / 600
Input
AC input voltage (Vac) : 220 - 240
AC input voltage window (Vac) (mains) : 140 - 300V 140 - 300V 140 - 300V 160 - 265V
Maximum AC input voltage (Vac) : 350
Minimum start-up AC voltage (Vac) : 150 150 150 170
Input frequency (Hz) : 50
Input frequency range : nominal ± 10 %
Typical no-load power consumption,
normal operation (W) : 12 12 27 27
AC input current (A) : 2.5 3.6 5 6.3
AC input fuse (A) : 5 5 6.3 10
Output
AC output voltage (Vac) : 230 (suitable for 220-240 Vac loads)
AC output voltage tolerance : nominal ± 5% (before battery low)
Output frequency (Hz) : 50
Output frequency stability (Hz) : < ± 0.1 (battery operation)
Output waveform : step sine wave
Power factor : 0.6 (0.7 at 90% load)
Transfer time (ms) : typically 4, max 10
Buck/Boost voltage regulation : if the input voltage is within the input voltage window,
the output voltage varies between 198-265Vac
Batteries (ratings given for 25°C)
Nominal voltage (Vdc) : 12 12 24 24
Number x capacity (Ah) of batteries : 1x5 1x7 2x5 2x7
Type : 12Vdc, sealed lead acid, maintenance free
Service life : up to 6 years (depending on use)
Recharge current (A) : 0.5 0.7 0.5 0.7
Battery recharge time for 80%
capacity (hours, approximation) : 3
Runtime in minutes
VA / Watts
100/ 60 25 40 60 85
350/210 3 8 14 24
500/300 - 3 7 11
700/420 - - 3 7
1000/600 - - - 3
General
Weight (kg) : 6.5 7.5 11 13
Dimensions (hxwxd, mm) : 150x110x300 150x110x420 150x110x450
Enclosure / protection : steel-plastic / IP20
Colour (operating panel / case) : RAL 9006 (aluminium) / RAL 7035 (light grey)
Environment
Safety : EN 50091-1-1 (EN 60950)
Electromagnetic compatibility : EN 50091-2
Ambient temperature : -10 to +40°C;
Sound at 1 meter : < 35 dB(A)
Maximum relative humidity : 95% (non-condensing)
7 - Specifications