Apart from the SNMP-option described in 4.4 the following options are possible:
5.1 Extended Runtime
Extended runtime can be obtained by connecting a separate battery extension module to the
UPS. The additional batteries increase the runtime and recharging time for the unit, all other
operational information is the same as for standard models.
5.2 TVSS (Transient Voltage Surge Suppressor)
RJ-45/RJ-11 Surge Protector.
To prevent damage caused by surges, noise and spikes traveling over the telephone line or
network line.
6.1 General Maintenance
Apart from battery servicing, the UPS is virtually maintenance free. Take care of proper
environmental conditions and keep air inlets/outlets free of dust. Please read 1.3.
6.2 Batteries - General
The service life of the battery is from 3 to 6 years, depending on the operating conditions
(mainly temperature and number of discharge cycles).
As a healthy battery is critical to the performance of the UPS, it is advised to regularly perform
a battery test to ensure failsafe operation (see section 3.3.3). When the condition of the battery
is critical, a
'replace battery'
alarm will be activated (see 3.1, LED 11). Replace the batteries as
soon as possible. See 6.3.
6.3 Batteries - Replacement
WARNING: first read the safety rules in sections 1.1, 1.2 and 1.4.
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
6.3.1 Battery replacement procedure 1kVA
1 Remove front panel
2 Unscrew five bolts of the battery compartment
3 Unplug battery connectors
4 Unscrew one bolt
5 Pull out the battery set
and renew it
6 Assemble UPS
by reverse procedure.
Fig. 6.1
5 - Optional Features
6 - Maintenance