Generac Power Systems 5465 Switch User Manual


 
Specifications
Surface Mount Annunciator
21 Light Remote Annunciator
Flush Mount Annunciator
Function Color Alarm Latched
Pre-Low Oil Pressure Yellow
n
Yes Yes
Pre-High Water Temp Yellow
n
Yes Yes
Pre Low Water Temp Yellow
n
Yes Yes
Pre-Low Fuel Yellow
n
Yes Yes
Battery Charge AC Fail Yellow
n
Yes No
Low Battery Voltage Yellow
n
Yes No
High Battery Voltage Yellow
n
No No
Not in Auto Red
n
Yes No
RPM Sensor Loss Red
n
Yes Yes
Overcrank Red
n
Yes Yes
Overspeed Red
n
Yes Yes
Low Oil Pressure Red
n
Yes Yes
Hi Water Temp Red
n
Yes Yes
Low Water Level Red
n
Yes Yes
Emergency Stop Red
n
Yes No
Gen Running Yellow
n
No No
Gen Power (ATS) Yellow
n
No No
Line Power (ATS) Green
n
No No
Systems Ready Green
n
Yes No
Communications OK Green
n
Yes No
Spare Green
n
No No
Spare Keypad Switch - Can be used to implement a remote start function. (Model 5464 only)
5.8
4.530.812 Dia.
0.812 Dia.
Both sides
0.86
9.06 1.64
2.32
6.49
11.42
8.27
9.64
Outside
Cut
Rough Opening
6.75 " x 9.88 "
Four mounting holes for
21 Light Annunciator
4-mm -0.7 Female Thread
1.57
Thru
R0.59
Both Sides
1.93
10.24
7.09
1.21
1.42
0.87
The 21-Light Annunciator can mount to
a flat surface with connections through
the 0.812 Dia. knockout on the back
surface or through 0.812 knockouts on
sides as shown.
This Flush Mount Box is recessed
into the wall opening and the sur-
face mount annunciator mounts to
the (4) 4 mm screw holes on the
back surface. After wire connec-
tions are made the front annuncia-
tor cover is attached.
Generac Power Systems, Inc. • P.O. Box 297, Whitewater, WI 53190 • guardiangenerators.com
©2008 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0177350SBY/Printed in U.S.A. 04.08, rev. 05.08