HP (Hewlett-Packard) HP T1000J Power Supply User Manual


 
SPECIFICATIONS
HP T750 G2, HP T750J, HP T1000 G3, HP T1000J, HP T1500 G3, and HP T1500J UPS Models User Guide S 505922-002
26
Table 8 Battery
UPS Configuration HP T750 G2: (2) 12V, 7 or 7.2 Ah internal batteries
HP T750J and HP T1000 G3: (2) 12V, 9 Ah internal batteries
HP T1000J, HP T1500 G3, and HP T1500J: (3) 12V, 9 Ah internal batteries
Voltage HP T750 G2, HP T750J, and HP T1000 G3: 24 Vdc
HP T1000J, HP T1500 G3, and HP T1500J: 36 Vdc
Type Sealed, maintenance‐free, valve‐regulated, lead‐acid
Charging Advanced charging for faster recovery; approximately 3 hours to 90% usable capacity at nominal line
and no supplementary power supply load
Monitoring Advanced monitoring for earlier failure detection and warning
Table 9 Battery Runtimes (in Minutes)
UPS Models by VA Ratings
Load (VA) Watts 750 1000 1400
200 128 38 41 58
300 192 27 28 41
500 320 14 15 28
600 402 9 10 19
750 503 6 8 14
900 603 6 10
1000 670 5 8
1200 804 6
1400 938 5
NOTE Battery times are approximate and may vary depending on the load configuration and battery charge.