HP (Hewlett-Packard) MA7200 Plus Power Supply User Manual


 
MA7200 PLUS Inverter 1 to 2 HP Fan Quick Start Manual
_______________________________________________________________
______________________________________________________________
TECO – Westinghouse Motor Company
4
Press the RUN key, and check the fan direction of rotation. If the direction is not correct, press
the STOP key and wait until the fan has come to a complete STOP. Next, power down the
inverter.
Danger
After the power has been turned OFF, wait at least 5 minutes until the charge
indicator extinguishes completely before touching any wiring, circuit boards or
components.
Reverse any two of the fan motor connections at the inverter ( U(T1),V(T2), or W(T3) ). Next,
following STEP 2, power-up the inverter; the motor direction should now be correct.
Step 5
– Select Method of Control
Before selecting the method of control, verify that the inverter is in the STOP mode.
There are two methods of control or combinations thereof that may be selected; Keypad and
Analog Signal.
RUN / STOP Command - Can be provided from the keypad or from an external contact
(see Fig. 2a).
Speed Reference – Can be from the keypad or from an external analog signal (0 – 10 VDC or
4 – 20 mA). see Fig’s 3a,3b, and 3c.
The RUN/STOP method of control is set by parameter Sn – 04 and the Speed Reference is set
by parameter Sn – 05. The following table shows the values to be set when selecting.
Value
Start / Stop
Sn – 04=
Speed Reference
Sn – 05=
*0 Keypad Keypad
1 External Contact External Analog
* NOTE
The factory default for Sn – 04 and Sn – 05 is set to 0; Digital Operator (Keypad) No
further parameter changes are necessary if this is the desired method of control. If
External Contact set to Sn – 04 or External Analog set to Sn – 05 is desired then proceed
as follows.