Hitachi AN091802-1 Power Supply User Manual


 
[2] DC voltage to be supplied
Supplied DC voltage should be between the UV voltage and the OV voltage (or BRD ON level) of the inverter.
Model name UV level BRD ON level OV level (regen.) OV level (source)
J100 200V class 140Vac ~ 160Vac (V-SET) +137.5V
390Vdc ± 15Vdc
400V class 280Vac ~ 320Vac (V-SET) +275V
780Vdc ± 30Vdc
J300 200V class 140Vac ~ 160Vac (AVR set) +138V 369Vdc ~ 404Vdc
400V class 280Vac ~ 320Vac (AVR set) +276V 756Vdc ~ 827Vdc
L100 200V class
190Vdc ± 10Vdc 395Vdc ± 20Vdc
Aprx. 365Vdc for 100s
400V class
395Vdc ± 20Vdc
-
790Vdc ± 40Vdc
Aprx. 730Vdc for 100s
SJ100 200V class 370Vdc +4%,-3%
400V class
Same as L100
740Vdc +4%,-3%
Same as L100 Same as L100
L300P 200V class
200Vdc ± 10Vdc 395Vdc ± 10Vdc
Aprx. 380Vdc for 60s
400V class
400Vdc ± 20Vdc
-
790Vdc ± 20Vdc
Aprx. 760Vdc for 60s
SJ300 200V class
400V class
Same as L300P
Adjustable by
[b096]
Same as L300P Same as L300P
Ø If it is higher, inverter may trip with OV or BRD error.
Ø If it is lower, inverter may trip with UV.
[3] Cautions
Case 1 : Connected parallel to a common DC net
Ø Take preventive measures to limit inrush current at power ON,
since the integrated inrush current limiting circuit is not used.
à Otherwise there will be a unexpected UV at net side or
damage to the inverter caused by V=di/dt.
Ø Use DC chokes for each inverter to avoid interaction due
to surge and/or harmonics.
à Otherwise there may be an unexpected failure of the
inverter or other attached equipment.
Ø Take preventive measures to ensure sufficient time between UV
level and dead voltage of the DC/DC converter (*1) at power
OFF. This is to allow ample time for EEPROM to store
the existing data at power OFF. (t ; see below)
à Otherwise there is a possibility of an EEPROM error at
the next power ON.
DC power
supply
Big inrush current at
power ON
INV #1
M 1
INV #2
M 2
INV #n
M n
UV level
Threshold voltage of DC-DC converter
(This value depends on the inverter model.
But in general it is around 100Vdc)
Main power (AC)
For Cases 2 & 3
OFF
DC-DC conv.
(internal 5V)
EEPROM store
period
DC bus voltage
For Cases 1~3
t
Around 0.5~1s or more
(*1) The required time depends on the parameters
which have changed before power OFF.