Engineering Guideline EH-150 Series PLC
8
Fieldbus Slave Modules
EH-IOCP
EH-IOCD
Profibus-DP
DeviceNet
General Type
Profibus-DP slave module for use with
standard I/O modules of EH-150 series
DeviceNet slave module for use with
standard I/O modules of EH-150 series
Function Max. number of base-racks 2 (2nd rack connected via EH-IOC) 2 (2nd rack connected via EH-IOC)
Max. number of modules
16
16
Node address range
1 - 99
1 - 63
Max. number of I/O's (with
64 point I/O modules
1024 1024
Max. input and output data 208 words 208 words
In data update cycle time
5ms
5ms
9.6 kbps
1200m
-
19.2 kbps
1200m
-
45.45 kbps
1200m
-
93.75 kbps
1200m
-
125 kbps
-
500m
187.5 kbps
1000m
-
250 kbps
-
250m
500 kbps
400m
100m
1500 kbps
200m
-
3 Mbps
100m
-
6 Mbps
100m
-
12 Mbps
100m
-
Approx. 600mA
Approx. 600mA
fixed at CPU-Slot
fixed at CPU-Slot
9 pin D-sub, female
5-pole DeviceNet connector
Double shielded twisted pair cables
according to Profibus specification
DeviceNet
TM
dedicated cable
System ROM/RAM check,
watch-dog timer check
System ROM/RAM check,
watch-dog timer check
GSD-file, File name:Hita049d.gsd.
This file can either be downloaded
from the web (www.hitachi-
ds.com/sub/info/updates) or received
directly from Hitachi Europe
EDS-file, File name: Absdev.eds.
This file can either be downloaded
from the web (www.hitachi-
ds.com/sub/info/updates) or received
directly from Hitachi Europe
Profibus configurator software,
Order-Number: PBDP-M-CONF
DeviceNet configurator RSNetworx
and dedicated interface adapter
File for configuration
Configurator software
Internal current consumption (5V)
I/O assignment
External connection
External wiring
Item
Fieldbus system
Max. segment
lenght (at data
transfer rate).
Self diagnosis