Honeywell QS7800B Network Card User Manual


 
QS7800B NETWORK INTERFACE CONTROLBUS™ MODULE FOR MULTI-DROPPING 7800 SERIES RELAY MODULES
65-0227—2 4
a. Near a phone line.
b. Within 4000 ft (1219 m) of all Relay Modules
connected to the Network Interface Unit.
c. Within 50 ft (15 m) of the personal computer
connected to the 25-pin RS-232 port of the Network
Interface Unit.
4. Mount the Network Interface Unit and insert the
ControlBus™ Module into the Network Interface Unit
slot, see Fig. 2 and 5.
Route the ControlBus™ cable so that all devices are
connected in a daisy chain configuration. It is
recommended that the QS7800B ControlBus™ Module be
at one end of the daisy chain.
5. Connect L1, L2 and Ground (GND) to the pigtails
(Q7700A only).
6. Insert the plug-in cards into the open slots of the
Network Interface Unit, starting with slot one.
7.
Install the covers, power wiring compartment and
Network Interface Unit.
8. Connect the serial port of the modem to the 9-pin
RS-232 connector of the Network Interface Unit (see
Fig 4).
9. Connect the serial port of the personal computer to the
25-pin RS-232C port on the Network Interface Unit for
local personal computer application, see Fig. 3.
10. Do not exceed 600 mA current draw, six card maximum,
total capacity of the plug-in cards. Refer to the
ControlBus™ Module device label and this specification
for individual loads.
11. Recheck all wiring with Fig. 6.
12. Restore power to the Network Interface Unit.
Fig. 1. QS7800B Network Interface ControlBus™ Module
dimensions in in. (mm).
Fig. 2. ControlBus™ Module mounting.
Fig. 3. RS-232 Interface insertion
(serial communications).
Fig. 4. Modem insertion, Network Interface Unit.
Fig. 5. ControlBus™ RS-485 interface insertion.
1 (25)
M2093
3-29/32
(99)
4-21/32 (118)
M7437B
ELECTRICAL
CONNECTOR
EDGE
CONNECTOR
CONTROLBUS™
MODULE
NETWORK
INTERFACE
UNIT
25-PIN
RS-232C
CONNECTOR
NETWORK
INTERFACE
UNIT
M7432B
CONTROLBUS
PLUG-IN MODULE
9-PIN RS-232
CONNECTOR
RS-232C CONNECTOR
(SERIAL COMMUNICATIONS)
M7433B
NETWORK
INTERFACE UNIT
CONTROLBUS
MODULE
CONTROLBUS
RS-485 CONNECTOR
NETWORK
INTERFACE UNIT
M7436B