Operating Parameters: Typical Schematic Diagram
* Service Factor:
-115% load continuously at 40 C ambient
-100% load continuously at 50 C ambient
-125% load for two hours at 40 C ambient
after 8 hours of 100% load operation
-200% load for one minute at 40 C ambient
after 8 hours of 100% load operation
-DC ripple 4.63 RMS at 100% resistive load
-DC voltage requlation 8% on 10% to 100%
load variation and 0% AC line variation
* Power factor 95% at 100% load
* Efficiency 95% or better at 100% load
* Approximate Dimensions for NEMA 2/3R Free Standing Enclosures
KW VOLTS DIMENSIONS KW VOLTS DIMENSIONS
3 240 DC 22W 14D 25H 25 240 DC 28W 18D 44H
5 240 DC 22W 14D 25H 30 240 DC
28W 18D 44H
7.5 240 DC 22W 14D 25H 40 240 DC
28W 18D 44H
10 240 DC 22W 14D 25H 50 240 DC
28W 18D 44H
12.5 240 DC 28W 18D 29H 60 240 DC
36W 24D 54H
15 240 DC 28W 18D 29H 75 240 DC
36W 24D 54H
20 240 DC 28W 18D 44H 100 240 DC
36W 24D 54H
* Dimensions Not For Construction Purposes