Hubbell Industrial Controls, Inc.
A subsidiary of Hubbell Inc.
4301 Cheyenne Drive, Archdale, N.C. 27263
Telephone (336) 434-2800 • FAX (336) 434-2803
http://www.hubbell-icd.com
sales@hubbell-icd.com
Key Components:
1. Manual transfer mechanism:
Normal-Off-Emergency
2. NEMA Type 1 enclosure
3. Power available light:
Emergency (optional)
4. Locking handles (optional)
5. Power available light: Normal
(optional)
6. Emergency source connection
7. Load connection
8. DPDT Auxiliary contacts
9. Normal source connection
10. Quick Break-Quick Make
contacts
LMTS Short Circuit Ratings:
with upsteam protective device as shown
Amp
Rating Fuse Size Amperage Breaker Size Amperage
(Amps-max.) (max.) (Amps-max.) (max.)
40 110 *10,000 100 10,000
60 110 *10,000 100 10,000
80 110 *10,000 100 10,000
100 110 *10,000 100 10,000
125 200 *100,000 200 25,000
200 200 *100,000 200 25,000
400 600 *100,000 600 50,000
600 600 *100,000 600 50,000
800 1,200 **100,000 1,200 50,000
1200 1,200 **100,000 1,200 50,000
1600 2,000 **100,000 2,000 65,000
2000 2,000 **100,000 2,000 65,000
2500 3,000 **200,000 3,000 25,000
3000 3,000 **200,000 3,000 30,000
4000 4,000 **200,000 4,000 30,000
*=Type RK5 fuse
**=Type L fuse
w/Circuit Breakerw/Current-Limitin
g
Fuse
Enclosure Dimensions & Weights
# of Poles Amp Rating H W D Wt.
2 & 3 40-100 14" 12" 8"
2 & 3 125-200 30" 30" 12" 150#
2 & 3 400 48" 36" 12" 425#
2 & 3 600 48" 36" 12" 450#
2 & 3 800 78" 60" 30" 600#
2 & 3 1200 78" 60" 30" 650#
2 & 3 1600-2000 91" 60" 30" 1400#
2 & 3 2500-3000 92" 60" 31"
2 & 3 4000 92" 60" 31"