IBM UPS1000TLV Power Supply User Manual


 
3
CAUTION! Handling Safety - Use safe practices when lifting.
<18 kg (<40 lb)
32–55 kg (70–120 lb)
18–32 kg (40–70 lb)
>55 kg (>120 lb)
>10º
CAUTION! Electrical Safety
Electrical Current from power, telephone, and communication cables is hazardous. Please read the following safety statements.
Do not connect or disconnect any cables or perform installation, maintenance, or reconfiguration of this product during an electrical storm.
Connect all power cords to a properly wired and grounded electrical outlet.
Connect to properly wired outlets any equipment that will be attached to this product.
When possible, use one hand only to connect or disconnect signal cables.
Never turn on any equipment when there is evidence of fire, water, or structural damage.
Disconnect the attached power cords, telecommunications systems, networks, and modems before you open the device covers, unless instructed otherwise
in the installation and configuration procedures.
Connect and disconnect cables as described in the following table when installing, moving, or opening covers on this product or attached devices.
To Connect: To Disconnect:
1. Turn everything OFF.
2. First attach all cables to devices.
3. Attach signal cables to connectors.
4. Attach power cords to outlet.
5. Turn device ON.
1. Turn everything OFF.
2. First remove power cords from outlet.
3. Remove signal cables from connectors.
4. Remove all cables from devices.
Do not work alone under hazardous conditions.
High current through conductive materials could cause severe burns.
Check that the power cord(s), plug(s), and sockets are in good condition.
Use qualified service personnel to change the plug on the uninterruptible power supply.
When grounding cannot be verified, disconnect the equipment from the utility power outlet before installing or connecting to other equipment. Reconnect
the power cord only after all connections are made.
Do not handle any metallic connector before the power has been disconnected.
Connect the equipment to a three wire utility outlet (two poles plus ground). The receptacle must be connected to appropriate branch circuit/mains protec-
tion (fuse or circuit breaker). Connection to any other type of receptacle may result in risk of electrical shock.
HV models only:
In order to maintain compliance with the EMC directive for products sold in Europe, output cords attached to the uninterruptible power supply
should not exceed 10 meters in length.
Total leakage current from connected equipment and the uninterruptible power supply must not exceed 3.5 mA for a pluggable A Type uninterrup-
tible power supply.
CAUTION! De-energizing Safety
The uninterruptible power supply has an internal energy source, the battery. The output may be energized when the unit is not connected to a utility power
outlet.
To de-energize the uninterruptible power supply, press the OFF button to shut the equipment off. Unplug the uninterruptible power supply from the utility
power outlet. Disconnect the external batteries where applicable and disconnect the internal battery (see Operation and Setup Guide). Push the ON button
to de-energize the capacitors.
CAUTION! Battery Safety
This equipment contains potentially hazardous voltages. Refer to your product documentation to determine which pats are user-replaceable.
Do not dispose of batteries in a fire; they may explode.
Do not open or mutilate batteries. They contain an electrolyte that is toxic and harmful to the skin and eyes.
To avoid personal injury due to energy hazard, remove wristwatches and jewelry such as rings when replacing the batteries. Use tools with insulated han-
dles.
Replace the battery module with the same number and type as originally installed in the equipment.
Be sure to deliver the spent battery to a recycling facility.