ICP DAS USA 8430 Network Card User Manual


 
#AASiCj
Command
#AASiCj(data)
Description
Sets the analog voltage output module data from the specified slot and
channel in the I-8000 unit. The data format is in engineering units only.
#AASiCj(data)[CHK](cr)
# A delimiter character
AA A 2-character HEX module address for the
specified I-8000 unit ,ranging from 01 to FFh
Si The specified slot number. i = 0 to 3(4 slots) or
i = 0 to 7(8 slots)
Cj The specified channel number.
i-87022 Î j = 0 to 1
i-87024 Î j = 0 to 3
i-87026 Î j = 0 to 3
i-8024 Î j = 0 to 3
(data) A decimal value, always engineer unit
[CHK] A 2-character checksum
Syntax
(cr) Carriage Return (0x0D) to denote the end of
command
Valid Command > [chk](cr)
Invalid Command ?AA[CHK](cr)
Any syntax or communication error may receive no response.
> A delimiter for valid command
? A delimiter for invalid command
AA A 2-character HEX module address
[CHK] A 2-character of checksum
(cr) Carriage Return (0x0D) to denote the end of
response
Command
#01S3C1+09.000
Response
> (cr)
Example 1:
Description This example sends the positive value +9.000V to
the Analog Data output Module in slot 3 and
channel 1 of the I-8000 unit at address 01h. The
response indicates the command is valid
Command
#01S3C1-05.000
Response
> (cr)
Example 2:
Description This example sends the negative value -5.000V to
the Analog Data output Module in slot 3 and
channel 1 of the I-8000 unit at address 01h. The
response indicates the command is valid
8430/8830/8KE4/8KE8 User’s manual, Jan 2005, Version 1.0, 8MS-002-10 ----- 74